View all text of Subpart 56.50 [§ 56.50-1 - § 56.50-110]
§ 56.50-97 - Piping for instruments, control, and sampling (modifies 122.3).
(a) Piping for instruments, control, and sampling must comply with paragraph 122.3 of ASME B31.1 (incorporated by reference; see § 56.01-2) except that:
(1) Soldered type fittings may not be used.
(2) The outside diameter of takeoff connections may not be less than 0.840 inches for service conditions up to 900 psig or 800 °F, and 1.050 inches for conditions that exceed either of these limits.
(b) [Reserved]