View all text of Subpart 113.20 [§ 113.20-1 - § 113.20-3]
§ 113.20-3 - Connection boxes.
Each connection box and each switch enclosure in an automatic sprinkler system must be constructed in accordance with Type 4 or 4X of NEMA 250 or IP 56 of IEC 60529:2013 (both incorporated by reference; see 46 CFR 110.10-1) requirements.