§ 111.85-1 - Electric oil immersion heaters.
Each oil immersion heater must have the following:
(a) An operating thermostat.
(b) Heating elements that have no electrical contact with the oil.
(c) A high temperature limiting device that:
(1) Opens all conductors to the heater;
(2) Is manually reset; and
(3) Actuates at a temperature below the flashpoint of the oil.
(d) Either—
(1) A low-fluid-level device that opens all conductors to the heater if the operating level drops below the manufacturer's recommended minimum safe level; or
(2) A flow device that opens all conductors to the heater if there is inadequate flow.