§ 111.53-1 - General.

(a) Each fuse must—

(1) Meet the general provisions of Article 240 of NFPA 70 or IEC 60092-202:2016 (both incorporated by reference; see Ҥ 110.10-1 of this subchapter) as appropriate.

(2) Have an interrupting rating sufficient to interrupt the asymmetrical RMS short-circuit current at the point of application; and

(b) Renewable link cartridge-type fuses must not be used.

(c) Each fuse installation must provide for ready access to test the condition of the fuse.