§ 111.05-31 - Grounding conductors for systems.
(a) A conductor for grounding a direct-current system must be the larger of:
(1) The largest conductor supplying the system; or
(2) No. 8 AWG (8.4mm 2).
(b) A conductor for grounding the neutral of an alternating-current system must meet Table 111.05-31(b).
Table 111.05-31(
Size of the largest generator cable or equivalent for parallel generators—AWG-MCM (mm 2) | Size of the system grounding conductor—AWG(mm 2) | Greater than | Less than or equal to | 2 (33.6) | 8 (8.4) | 2 (33.6) | 0 (53.5) | 6 (13.3) | 0 (53.5) | 3/0 (85.0) | 4 (21.2) | 3/0 (85.0) | 350 MCM (177) | 2 (33.6) | 350 MCM (177) | 600 MCM (304) | 0 (53.5) | 600 MCM (304) | 1100 MCM (557) | 2/0 (67.5) | 1100 MCM (557) | 3/0 (85.0) |
---|