§ 108.495 - Locations and number of fire extinguishers required.

Table 1 to § 108.495 indicates the minimum required number and type of fire extinguishers for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.

Table 1 to § 108.495—Carriage of Portable Fire Extinguishers

Space Minimum
required
rating
Quantity and location Safety AreasWheelhouse and control room20-B:C2 in the vicinity of the exit. Stairway and elevator enclosureNone required. Corridors2-A1 in each corridor not more than 150 ft (45 m) apart. (May be located in stairways.) Lifeboat embarkation and lowering stationsNone required. Radio room10-B:C2 in the vicinity of the exit. AccommodationsStaterooms, toilet spaces, public spaces, offices, lockers, small storerooms, pantries, open decks, and similar spacesNone required. Service SpacesGalleys40-B:C1 for each 2,500 sq ft (232.2 sq m) or fraction thereof suitable for the hazards involved. Paint and lamp rooms40:B1 outside each room in the vicinity of the exit. Storerooms2-A1 for each 2,500 sq ft (232.2 sq m) or fraction thereof located in the vicinity of the exits, either inside or outside the spaces. Workshop and similar spaces20-B:C1 outside each space in the vicinity of the exit. Machinery SpacesOil-fired boilers: Spaces containing oil-fired boilers, either main or auxiliary, or their fuel oil units40-B2 required in each space. 160-B1 required in each space. See note 1. Internal combustion or gas turbine propelling machinery spaces40-B1 for each 1,000 brake horsepower but not less than 2 and not more than 6 in each space. 120-B1 required in each space. See note 1. Motors or generators of electric propelling machinery that do not have an enclosed ventilating system40-B:C1 for each motor or generator. Motors and generators of electric propelling machinery that have enclosed ventilating systemsNone required. Auxiliary SpacesInternal combustion engines or gas turbine40-B1 outside the space containing engines or turbines in the vicinity of the exit. Electric emergency motors or generators40-B:C1 outside the space containing motors or generators in the vicinity of the exit. Steam driven auxiliary machineryNone required. Trunks to machinery spacesNone required. Fuel tanksNone required. Miscellaneous AreasHelicopter landing decks160-B1 at each access route. Helicopter fueling facilities160-B1 at each fuel transfer facility. See note 2. Drill floor40-B:C2 required. Cranes with internal combustion engines40-B:C1 required. Spare Units2-A10 percent of the total required rounded up. 40-B:C10 percent of the total required rounded up.

1 Not required where a fixed gas extinguishing system is installed.

2 Not required where a fixed foam system is installed in accordance with § 108.489.

[USCG-2012-0196, 81 FR 48266, July 22, 2016, as amended by USCG-2020-0519, 89 FR 76699, Sept. 18, 2024]