§ 108.441 - Piping and discharge rates for CO2 systems.
(a) The size of branch lines to spaces protected by a CO
(b) Distribution piping within a space must be proportioned from the supply line to give proper distribution to the outlets without throttling.
(c) The number, type, and location of discharge outlets must distribute the CO
Table 108.441—
CO | Minimum pipe size (inches), millimeters (inches) | 45 (100) | 12.7 ( 1/2). | 104 (225) | 19.05 ( 3/4). | 136 (300) | 25.4 (1). | 272 (600) | 31.75 (1 1/4). | 450 (1,000) | 38.10 (1 1/2). | 1,110 (2,450) | 50.80 (2). | 1,130 (2,500) | 63.5 (2 1/2). | 2,023 (4,450) | 76.2 (3). | 3,229 (7,100) | 88.9 (3 1/2). | 4,750 (10,000) | 101.6 (4). | 6,818 (15,000) | 114.3 (4 1/2). |
---|
(d) The total area of all discharge outlets must be more than 35 percent and less than 85 percent of the nominal cylinder outlet area or the area of the supply pipe, whichever is smaller. The nominal cylinder outlet area in square centimeters is determined by multiplying the factor 0.0313 by the number of kilograms of CO
(e) A CO