- Table 4 to Subpart IIII of Part 60—Emission Standards for Stationary Fire Pump Engines
[As stated in §§ 60.4202(d) and 60.4205(c), you must comply with the following emission standards for stationary fire pump engines]
Maximum engine power | Model year(s) | Emission standards for stationary fire pump engines in g/KW-hr
(g/HP-hr) | NMHC + NO | CO | PM | KW<8 (HP<11) | 2010 and earlier | 10.5 (7.8) | 8.0 (6.0) | 1.0 (0.75) | KW<8 (HP<11) | 2011 + | 7.5 (5.6) | 8.0 (6.0) | 0.40 (0.30) | 8≤KW<19 (11≤HP<25) | 2010 and earlier | 9.5 (7.1) | 6.6 (4.9) | 0.80 (0.60) | 8≤KW<19 (11≤HP<25) | 2011 + | 7.5 (5.6) | 6.6 (4.9) | 0.40 (0.30) | 19≤KW<37 (25≤HP<50) | 2010 and earlier | 9.5 (7.1) | 5.5 (4.1) | 0.80 (0.60) | 19≤KW<37 (25≤HP<50) | 2011 + | 7.5 (5.6) | 5.5 (4.1) | 0.30 (0.22) | 37≤KW<56 (50≤HP<75) | 2010 and earlier | 10.5 (7.8) | 5.0 (3.7) | 0.80 (0.60) | 37≤KW<56 (50≤HP<75) | 2011 + 1 | 4.7 (3.5) | 5.0 (3.7) | 0.40 (0.30) | 56≤KW<75 (75≤HP<100) | 2010 and earlier | 10.5 (7.8) | 5.0 (3.7) | 0.80 (0.60) | 56≤KW<75 (75≤HP<100) | 2011 + 1 | 4.7 (3.5) | 5.0 (3.7) | 0.40 (0.30) | 75≤KW<130 (100≤HP<175) | 2009 and earlier | 10.5 (7.8) | 5.0 (3.7) | 0.80 (0.60) | 75≤KW<130 (100≤HP<175) | 2010 + 2 | 4.0 (3.0) | 5.0 (3.7) | 0.30 (0.22) | 130≤KW<225 (175≤HP<300) | 2008 and earlier | 10.5 (7.8) | 3.5 (2.6) | 0.54 (0.40) | 130≤KW<225 (175≤HP<300) | 2009 + 3 | 4.0 (3.0) | 3.5 (2.6) | 0.20 (0.15) | 225≤KW<450 (300≤HP<600) | 2008 and earlier | 10.5 (7.8) | 3.5 (2.6) | 0.54 (0.40) | 225≤KW<450 (300≤HP<600) | 2009 + 3 | 4.0 (3.0) | 3.5 (2.6) | 0.20 (0.15) | 450≤KW≤560 (600≤HP≤750) | 2008 and earlier | 10.5 (7.8) | 3.5 (2.6) | 0.54 (0.40) | 450≤KW≤560 (600≤HP≤750) | 2009 + | 4.0 (3.0) | 3.5 (2.6) | 0.20 (0.15) | KW>560 (HP>750) | 2007 and earlier | 10.5 (7.8) | 3.5 (2.6) | 0.54 (0.40) | KW>560 (HP>750) | 2008 + | 6.4 (4.8) | 3.5 (2.6) | 0.20 (0.15) |
---|
1 For model years 2011-2013, manufacturers, owners and operators of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 revolutions per minute (rpm) may comply with the emission limitations for 2010 model year engines.
2 For model years 2010-2012, manufacturers, owners and operators of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 rpm may comply with the emission limitations for 2009 model year engines.
3 In model years 2009-2011, manufacturers of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 rpm may comply with the emission limitations for 2008 model year engines.