- Table 3 to Subpart DDDD of Part 60—Model Rule—Operating Limits for Wet Scrubbers
For these operating
parameters | You must establish these operating limits | And monitor using these minimum frequencies | Data
measurement | Data
recording | Averaging time | Charge rate | Maximum charge rate | Continuous | Every hour | Daily (batch units). 3-hour rolling (continuous and intermittent units). 1 | Pressure drop across the wet scrubber or amperage to wet scrubber | Minimum pressure drop or amperage | Continuous | Every 15 minutes | 3-hour rolling. 1 | Scrubber liquor flow rate | Minimum flow rate | Continuous | Every 15 minutes | 3-hour rolling. 1 | Scrubber liquor pH | Minimum pH | Continuous | Every 15 minutes | 3-hour rolling. 1 |
---|
1 Calculated each hour as the average of the previous 3 operating hours.