Operating parameters to be monitored
| Minimum frequency
| Control system
| Data measurement
| Data recording
| Dry scrubber followed by fabric filter
| Wet scrubber
| Dry scrubber followed by fabric filter and wet scrubber
| Maximum operating parameters:
| | | | | | Maximum charge rate | Continuous | 1 × hour | ✔ | ✔ | ✔
| Maximum fabric filter inlet temperature | Continuous | 1 × minute | ✔ | | ✔
| Maximum flue gas temperature | Continuous | 1 × minute | ✔ | ✔
| | Minimum operating parameters:
| | | | | | Minimum secondary chamber temperature | Continuous | 1 × minute | ✔ | ✔ | ✔
| Minimum dioxin/furan sorbent flow rate | Hourly | 1 × hour | ✔ | | ✔
| Minimum HCI sorbent flow rate | Hourly | 1 × hour | ✔ | | ✔
| Minimum mercury (Hg) sorbent flow rate | Hourly | 1 × hour | ✔ | | ✔
| Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubber | Continuous | 1 × minute | | ✔ | ✔
| Minimum scrubber liquor flow rate | Continuous | 1 × minute | | ✔ | ✔
| Minimum scrubber liquor pH | Continuous | 1 × minute | | ✔ | ✔ |