View all text of Part 133 [§ 133.100 - § 133.105]
§ 133.105 - Treatment equivalent to secondary treatment.
This section describes the minimum level of effluent quality attainable by facilities eligible for treatment equivalent to secondary treatment (§ 133.101(g)) in terms of the parameters—BOD
(a) BOD
(2) The 7-day average shall not exceed 65 mg/l.
(3) The 30-day average percent removal shall not be less than 65 percent.
(b) SS. Except where SS values have been adjusted in accordance with § 133.103(c):
(1) The 30-day average shall not exceed 45 mg/l.
(2) The 7-day average shall not exceed 65 mg/l.
(3) The 30-day average percent removal shall not be less than 65 percent.
(c) pH. The requirements of § 133.102(c) shall be met.
(d) Alternative State requirements. Except as limited by paragraph (f) of this section, and after notice and opportunity for public comment, the Regional Administrator, or, if appropriate, State Director subject to EPA approval, is authorized to adjust the minimum levels of effluent quality set forth in paragraphs (a)(1), (a)(2), (b)(1) and (b)(2) of this section for trickling filter facilities and in paragraphs (a)(1) and (a)(2) of this section for waste stabilization pond facilities, to conform to the BOD
(e) CBOD
(1) Where data are available to establish CBOD
(i) The 30-day average shall not exceed 40 mg/l.
(ii) The 7-days average shall not exceed 60 mg/l.
(iii) The 30-day average percent removal shall not be less than 65 percent.
(2) Where data are available, the parameter CBOD
(f) Permit adjustments. Any permit adjustment made pursuant to this part may not be any less stringent than the limitations required pursuant to § 133.105(a)-(e). Furthermore, permitting authorities shall require more stringent limitations when adjusting permits if: (1) For existing facilities the permitting authority determines that the 30-day average and 7-day average BOD
(2) For new facilities, the permitting authority determines that the 30-day average and 7-day average BOD