Appendix I - Appendix I to Subpart D of Part 18

LIST OF TABLES

Table No. Title 1Portable power cable ampacities—600 volts. 2Portable cord ampacities—600 volts. 3Portable power cable ampacities—601 to 5,000 volts. 4Normal diameter of round cables with tolerances in inches—600 volts. 5Nominal dimension of flat cables with tolerances in inches—600 volts. 6Nominal diameter of heavy jacketed cords with tolerances in inches—600 volts. 7Nominal diameter of three-conductor portable power cables with tolerances in inches—601 to 5,000 volts. 8Fuse ratings or instantaneous settings of circuit breakers for short-circuit protection of portable cables. 9Specifications for portable cables longer than 500 feet. 10High voltage trailing cable ampacities and outside diameters.

Table 1—Portable Power Cable Ampacities—600 Volts (Amperes Per Conductor Based on 60 °C. Copper Temperature—40 °C. Ambient)

Conductor size—AWG or MCM Single conductor 2-conductor, round or flat 3-conductor, round or flat 4-conductor 5-conductor 6-conductor 8454035302520 6605050403530 4857065554535 3958075655545 21109590756555 1130110100857565 1/01501301201009080 2/017515013511510595 3/0205175155130120110 4/0235200180150140130 250275220200160300305240220175350345240235190400375280250200450400300270215500425320290230

Table 2—Portable Cord Ampacities—600 Volts (Amperes Per Conductor Based on 60 °C. Copper Temperature—40 °C. Ambient)

Conductor size—AWG 1-3 conductor 4-6 conductor 7-9 conductor 1415128 12201611 10252014

Table 3—Portable Power Cable Ampacities—601 to 5,000 Volts (Amperes Per Conductor Based on 75 °C. Copper Temperature—40 °C. Ambient)

Conductor size—AWG or MCM 3-conductor types G-GC and SIIC-GC 2,000 volts 3-conductor type SHD-GC 2,001-5,000 volts 66565 48585 3100100 2115115 1130130 1/0145145 2/0170170 3/0195195 4/0220220 250245245 300275275 350305305

Table 4—Nominal Diameters of Round Cables With Tolerances in Inches—600 Volts

Conductor size—AWG or MCM Single conductor 2-conductor 3-conductor 4-conductor—Types W & G 5-conductor—Types W & G 6-conductor Types W & G twisted Type PG, 2 power Type PCG, 3 power, ground Types W & G Type PG, 3 power, ground Type PCG, 3 power, 2 control, ground Type w Tolerance 80.440.810.840.940.910.931.030.991.071.18±0.03 6.51.93.93.981.011.031.181.101.211.31±.03 4.571.081.081.101.171.201.291.271.401.52±.03 3.631.171.171.201.241.271.311.341.481.61±.03 2.661.271.271.291.341.341.391.481.611.75±.03 1.741.441.441.441.511.521.521.681.882.05±.03 1/0.771.521.521.521.651.681.681.791.962.13±.04 2/0.821.651.651.651.751.791.791.932.132.32±.04 3/0.871.771.771.771.891.931.932.072.262.49±.05 4/0.931.921.921.922.042.132.132.262.462.71±.05 2501.032.162.162.162.392.392.392.66±.06 3001.092.322.562.84±.06 3501.152.432.682.98±.06 4001.202.572.823.14±.06 4501.262.672.943.26±.06 5001.312.763.033.40±.06

Table 5—Nominal Dimensions of Flat Cables With Tolerances in Inches—600 Volts

Conductor size—AWG 2-conductor 3-conductor—Type G Type W Type G Major Minor Major Minor Major Minor O.D. Tolerance O.D. Tolerance O.D. Tolerance O.D. Tolerance O.D. Tolerance O.D. Tolerance 80.84±0.040.51±0.03 6.93±.04.56±.031.02±.040.56±.031.65±0.060.67±0.05 41.05±.04.61±.031.15±.04.61±.031.85±.06.75±.05 31.14±.04.68±.031.26±.04.68±.031.99±.06.77±.05 21.24±.04.73±.031.35±.04.73±.062.10±.06.81±.05 11.40±.04.81±.031.55±.04.81±.032.43±.06.97±.05 1/01.51±.04.93±.031.67±.04.93±.03 2/01.63±.04.99±.031.85±.04.99±.03 3/01.77±.041.03±.032.00±.041.03±.03 4/01.89±.041.10±.032.10±.041.10±.03

Table 6—Nominal Diameters of Heavy Jacketed Cords With Tolerances In Inches—600 Volts

Conductor size—AWG 2-conductor 3-conductor 4-conductor 5-conductor 6-conductor 7-conductor Diameter Tolerance Diameter Tolerance Diameter Tolerance Diameter Tolerance Diameter Tolerance Diameter Tolerance 140.64±0.020.67±0.020.71±0.020.78±0.030.83±0.030.89±0.03 12.68±.02.72±.03.76±.03.83±.03.89±.03.98±.03 10.73±.03.80±.03.84±.03.90±.031.00±.031.07±.03

Table 7—Nominal Diameters of Three-Conductor Portable Power Cables With Tolerances in Inches—601 to 5,000 Volts

Conductor size—AWG or MCM Type G-GC (nonshielded) 2,000 volts Type SHC-GC (shielded overall) 2,000 volts Type SHD-GC (individually shielded power conductors) 2,001-3,000 volts Type SHD-GC (individually shielded power conductors) 3,001-5,000 volts Diameter Tolerance Diameter Tolerance Diameter Tolerance Diameter Tolerance 61.25 + 0.10, −0.061.39 + 0.11, −0.071.62 + 0.13, −0.081.78 + 0.14, −0.09 41.40 + .11, −.071.55 + .12, −.081.77 + .14, −.091.90 + .15, −.10 31.48 + .12, −.071.62 + .13, −.081.84 + .15, −.091.98 + .16, −.10 21.55 + .12, −.081.71 + .14, −.091.92 + .15, −.102.09 + .17, −.11 11.74 + .14, −.091.89 + .15, −.092.04 + .16, −.102.18 + .17, −.11 1/01.84 + .15, −.092.02 + .16, −.102.18 + .17, −.112.34 + .19, −.12 2/01.99 + .16, −.102.16 + .17, −.112.29 + .18, −.122.46 + .20, −.12 3/02.12 + .17, −.112.30 + .18, −.112.45 + .20, −.122.62 + .21, −.13 4/02.30 + .18, −.122.48 + .20, −.122.62 + .21, −.132.76 + .22, −.14 2502.46 + .20, −.122.70 + .22, −.133002.63 + .21, −.132.84 + .23, −.143502.75 + .22, −.142.97 + .24, −.15

Table 8—Fuse Ratings or Instantaneous Setting of Circuit Breakers for Short-Circuit Protection of Portable Cables and Cords

Conductor size—AWG or MCM Ohms/1,000 ft. at 25 °C. Maximum allowable fuse rating (amperes) Maximum allowable circuit breaker instantaneous setting (amperes) 1142.622050 121.653075 101.0440150 8.65480200 6.410100300 4.259200500 3.205250600 2.162300800 1.1293751,000 1/0.1025001,250 2/0.0811,500 3/0.0642,000 4/0.0512,500 250.0432,500 300.0362,500 350.0312,500 400.0272,500 450.0242,500 500.0222,500

1 Higher circuit-breaker settings may be permitted for special applications when justified.

Table 9—Specifications for Portable Cables Longer Than 500 Feet 1

Conductor size—AWG or MCM Max. allowable length (feet) Normal ampacity at 60 °C. copper temperature (40 °C. ambient) Resistance at 60 °C. copper temperature (ohms) 6550500.512 460070.353 365080.302 270095.258 1750110.220 1/0800130.185 2/0850150.157 3/0900175.130 4/01,000200.116 2501,000220.098 3001,000240.082 3501,000260.070 4001,000280.061 4501,000300.054 5001,000320.050

1 Fuses shall not be used for short-circuit protection of these cables. Circuit breakers shall be used with the instantaneous trip settings not to exceed the values given in Table 8.

Table 10—High Voltage Trailing Cable Ampacities and Outside Diameters

Power conductor Ampacity * Outside diameter **
(inches)
Size AWG or kcmil Amperes per conductor SHD-GC 2001 to 5000 volts SHD-CGC 2001 to 5000 volts SHD-PCG 2001 to 5000 volts 6931.561.62 41221.681.73 31401.781.821.94 21591.871.912.03 11841.951.982.12 1/02112.082.102.26 2/02432.202.202.40 3/02792.362.362.58 4/03212.502.502.76 2503552.692.69 3003982.812.81 3504352.952.95 5005363.313.31

* These ampacities are based on single isolated conductor in air, operated with open-circuited shield for a 90 °C conductor temperature and an ambient temperature of 40 °C.

** Tolerances for the outside diameter are + 8%/−5%.

[33 FR 4660, Mar. 19, 1968; 33 FR 6345, Apr. 26, 1968, as amended at 42 FR 8373, Feb. 10, 1977; 75 FR 17549, Apr. 6, 2010; 75 FR 20918, Apr. 22, 2010]