§ 431.97 - Energy efficiency standards and their compliance dates.
(a) All basic models of commercial package air conditioning and heating equipment must be tested for performance using the applicable DOE test procedure in § 431.96, be compliant with the applicable standards set forth in paragraphs (b) through (i) of this section, and be certified to the Department under 10 CFR part 429.
(b) Each air-cooled commercial package air conditioning and heating equipment (excluding air-cooled equipment with cooling capacity less than 65,000 Btu/h and double-duct air conditioners or heat pumps) manufactured on or after January 1, 2023, and before January 1, 2029, must meet the applicable minimum energy efficiency standard level(s) set forth in table 1 to this paragraph (b). Each air-cooled commercial package air conditioning and heating equipment (excluding air-cooled equipment with cooling capacity less than 65,000 Btu/h and double-duct air conditioners or heat pumps) manufactured on or after January 1, 2029, must meet the applicable minimum energy efficiency standard level(s) set forth in table 2 to this paragraph (b). Each water-cooled commercial package air conditioning and heating equipment manufactured on or after the compliance date listed in table 3 to this paragraph (b) must meet the applicable minimum energy efficiency standard level(s) set forth in table 3. Each evaporatively-cooled commercial air conditioning and heating equipment manufactured on or after the compliance date listed in table 4 to this paragraph (b) must meet the applicable minimum energy efficiency standard level(s) set forth in table 4. Each double-duct air conditioner or heat pump manufactured on or after January 1, 2010, must meet the applicable minimum energy efficiency standard level(s) set forth in table 5 to this paragraph (b).
Table 1 to Paragraph (
Cooling capacity | Subcategory | Supplementary heating type | Minimum
efficiency 1 | Compliance date: equipment
manufactured starting on . . . | ≥65,000 Btu/h and <135,000 Btu/h | AC | Electric Resistance Heating or No Heating | IEER = 14.8 | January 1, 2023. | ≥65,000 Btu/h and <135,000 Btu/h | AC | All Other Types of Heating | IEER = 14.6 | January 1, 2023. | ≥65,000 Btu/h and <135,000 Btu/h | HP | Electric Resistance Heating or No Heating | IEER = 14.1
COP = 3.4 | January 1, 2023. | ≥65,000 Btu/h and <135,000 Btu/h | HP | All Other Types of Heating | IEER = 13.9
COP = 3.4 | January 1, 2023. | ≥135,000 Btu/h and <240,000 Btu/h | AC | Electric Resistance Heating or No Heating | IEER = 14.2 | January 1, 2023. | ≥135,000 Btu/h and <240,000 Btu/h | AC | All Other Types of Heating | IEER = 14.0 | January 1, 2023. | ≥135,000 Btu/h and <240,000 Btu/h | HP | Electric Resistance Heating or No Heating | IEER = 13.5
COP = 3.3 | January 1, 2023. | ≥135,000 Btu/h and <240,000 Btu/h | HP | All Other Types of Heating | IEER = 13.3
COP = 3.3 | January 1, 2023. | ≥240,000 Btu/h and <760,000 Btu/h | AC | Electric Resistance Heating or No Heating | IEER = 13.2 | January 1, 2023. | ≥240,000 Btu/h and <760,000 Btu/h | AC | All Other Types of Heating | IEER = 13.0 | January 1, 2023. | ≥240,000 Btu/h and <760,000 Btu/h | HP | Electric Resistance Heating or No Heating | IEER = 12.5
COP = 3.2 | January 1, 2023. | ≥240,000 Btu/h and <760,000 Btu/h | HP | All Other Types of Heating | IEER = 12.3
COP = 3.2 | January 1, 2023. |
---|
1 See section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.
Table 2 to Paragraph (
Cooling capacity | Subcategory | Supplementary heating type | Minimum efficiency | Compliance date: equipment
manufactured starting on . . . | ≥65,000 Btu/h and <135,000 Btu/h | AC | Electric Resistance Heating or No Heating | IVEC = 14.3 | January 1, 2029. | ≥65,000 Btu/h and <135,000 Btu/h | AC | All Other Types of Heating | IVEC = 13.8 | January 1, 2029. | ≥65,000 Btu/h and <135,000 Btu/h | HP | All Types of Heating | IVEC = 13.4
IVHE = 6.2 | January 1, 2029. | ≥135,000 Btu/h and <240,000 Btu/h | AC | Electric Resistance Heating or No Heating | IVEC = 13.8 | January 1, 2029. | ≥135,000 Btu/h and <240,000 Btu/h | AC | All Other Types of Heating | IVEC = 13.3 | January 1, 2029. | ≥135,000 Btu/h and <240,000 Btu/h | HP | All Types of Heating | IVEC = 13.1
IVHE = 6.0 | January 1, 2029. | ≥240,000 Btu/h and <760,000 Btu/h | AC | Electric Resistance Heating or No Heating | IVEC = 12.9 | January 1, 2029. | ≥240,000 Btu/h and <760,000 Btu/h | AC | All Other Types of Heating | IVEC = 12.2 | January 1, 2029. | ≥240,000 Btu/h and <760,000 Btu/h | HP | All Types of Heating | IVEC = 12.1
IVHE = 5.8 | January 1, 2029. |
---|
Table 3 to Paragraph (
Cooling capacity | Supplementary heating type | Minimum efficiency | Compliance date: equipment
manufactured starting on . . . | <65,000 Btu/h | All | EER = 12.1 | October 29, 2003. | ≥65,000 Btu/h and <135,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.1 | June 1, 2013. | ≥65,000 Btu/h and <135,000 Btu/h | All Other Types of Heating | EER = 11.9 | June 1, 2013. | ≥135,000 Btu/h and <240,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.5 | June 1, 2014. | ≥135,000 Btu/h and <240,000 Btu/h | All Other Types of Heating | EER = 12.3 | June 1, 2014. | ≥240,000 Btu/h and <760,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.4 | June 1, 2014. | ≥240,000 Btu/h and <760,000 Btu/h | All Other Types of Heating | EER = 12.2 | June 1, 2014. |
---|
Table 4 to Paragraph (
Cooling capacity | Supplementary heating type | Minimum efficiency | Compliance date: equipment
manufactured starting on . . . | <65,000 Btu/h | All | EER = 12.1 | October 29, 2003. | ≥65,000 Btu/h and <135,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.1 | June 1, 2013. | ≥65,000 Btu/h and <135,000 Btu/h | All Other Types of Heating | EER = 11.9 | June 1, 2013. | ≥135,000 Btu/h and <240,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.0 | June 1, 2014. | ≥135,000 Btu/h and <240,000 Btu/h | All Other Types of Heating | EER = 11.8 | June 1, 2014. | ≥240,000 Btu/h and <760,000 Btu/h | No Heating or Electric Resistance Heating | EER = 11.9 | June 1, 2014. | ≥240,000 Btu/h and <760,000 Btu/h | All Other Types of Heating | EER = 11.7 | June 1, 2014. |
---|
Table 5 to Paragraph (
Cooling capacity | Subcategory | Supplementary heating type | Minimum
efficiency 1 | Compliance date: equipment
manufactured starting on . . . | ≥65,000 Btu/h and <135,000 Btu/h | AC | Electric Resistance Heating or No Heating | EER = 11.2 | January 1, 2010. | ≥65,000 Btu/h and <135,000 Btu/h | AC | All Other Types of Heating | EER = 11.0 | January 1, 2010. | ≥65,000 Btu/h and <135,000 Btu/h | HP | Electric Resistance Heating or No Heating | EER = 11.0
COP = 3.3 | January 1, 2010. | ≥65,000 Btu/h and <135,000 Btu/h | HP | All Other Types of Heating | EER = 10.8
COP = 3.3 | January 1, 2010. | ≥135,000 Btu/h and <240,000 Btu/h | AC | Electric Resistance Heating or No Heating | EER = 11.0 | January 1, 2010. | ≥135,000 Btu/h and <240,000 Btu/h | AC | All Other Types of Heating | EER = 10.8 | January 1, 2010. | ≥135,000 Btu/h and <240,000 Btu/h | HP | Electric Resistance Heating or No Heating | EER = 10.6
COP = 3.2 | January 1, 2010. | ≥135,000 Btu/h and <240,000 Btu/h | HP | All Other Types of Heating | EER = 10.4
COP = 3.2 | January 1, 2010. | ≥240,000 Btu/h and <300,000 Btu/h | AC | Electric Resistance Heating or No Heating | EER = 10.0 | January 1, 2010. | ≥240,000 Btu/h and <300,000 Btu/h | AC | All Other Types of Heating | EER = 9.8 | January 1, 2010. | ≥240,000 Btu/h and <300,000 Btu/h | HP | Electric Resistance Heating or No Heating | EER = 9.5
COP = 3.2 | January 1, 2010. | ≥240,000 Btu/h and <300,000 Btu/h | HP | All Other Types of Heating | EER = 9.3
COP = 3.2 | January 1, 2010. |
---|
1 See section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.
(c) Each water-source heat pump manufactured starting on the compliance date listed in table 6 to this paragraph (c) must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (c).
Table 6 to Paragraph (
Cooling capacity | Minimum efficiency | Compliance date: equipment
manufactured starting on . . . | <17,000 Btu/h | EER = 12.2
COP = 4.3 | October 9, 2015. | ≥17,000 Btu/h and <65,000 Btu/h | EER = 13.0
COP = 4.3 | October 9, 2015. | ≥65,000 Btu/h and <135,000 Btu/h | EER = 13.0
COP = 4.3 | October 9, 2015. |
---|
(d) Each non-standard size packaged terminal air conditioner (PTAC) and packaged terminal heat pump (PTHP) manufactured on or after October 7, 2010, must meet the applicable minimum energy efficiency standard level(s) set forth in table 7 to this paragraph (d). Each standard size PTAC manufactured on or after October 8, 2012, and before January 1, 2017, must meet the applicable minimum energy efficiency standard level(s) set forth in table 7. Each standard size PTHP manufactured on or after October 8, 2012, must meet the applicable minimum energy efficiency standard level(s) set forth in table 7. Each standard size PTAC manufactured on or after January 1, 2017, must meet the applicable minimum energy efficiency standard level(s) set forth in table 8 to this paragraph (d).
Table 7 to Paragraph (
Equipment type | Category | Cooling capacity | Minimum efficiency | Compliance date: products
manufactured on and after . . . | PTAC | Standard Size | <7,000 Btu/h | EER = 11.7 | October 8, 2012. 2 | ≥7,000 Btu/h and ≤15,000 Btu/h | EER = 13.8−(0.3 × Cap 1) | October 8, 2012. 2 | >15,000 Btu/h | EER = 9.3 | October 8, 2012. 2 | Non-Standard Size | <7,000 Btu/h | EER = 9.4 | October 7, 2010. | ≥7,000 Btu/h and ≤15,000 Btu/h | EER = 10.9−(0.213 × Cap 1) | October 7, 2010. | >15,000 Btu/h | EER = 7.7 | October 7, 2010. | PTHP | Standard Size | <7,000 Btu/h | EER = 11.9
COP = 3.3 | October 8, 2012. | ≥7,000 Btu/h and ≤15,000 Btu/h | EER = 14.0−(0.3 × Cap
1)
COP = 3.7−(0.052 × Cap 1) | October 8, 2012. | >15,000 Btu/h | EER = 9.5
COP = 2.9 | October 8, 2012. | Non-Standard Size | <7,000 Btu/h | EER = 9.3
COP = 2.7 | October 7, 2010. | ≥7,000 Btu/h and ≤15,000 Btu/h | EER = 10.8−(0.213 × Cap
1)
COP = 2.9−(0.026 × Cap 1) | October 7, 2010. | >15,000 Btu/h | EER = 7.6
COP = 2.5 | October 7, 2010. |
---|
1 “Cap” means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.
2 And manufactured before January 1, 2017. See table 8 to this paragraph (d) for updated efficiency standards that apply to this category of equipment manufactured on and after January 1, 2017.
Table 8 to Paragraph (
Equipment type | Category | Cooling capacity | Minimum efficiency | Compliance date: products
manufactured on and after . . . | PTAC | Standard Size | <7,000 Btu/h | EER = 11.9 | January 1, 2017. | ≥7,000 Btu/h and ≤15,000 Btu/h | EER = 14.0−(0.3 × Cap 1) | January 1, 2017. | >15,000 Btu/h | EER = 9.5 | January 1, 2017. |
---|
1 “Cap” means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.
(e)(1) Each single package vertical air conditioner and single package vertical heat pump manufactured on or after January 1, 2010, but before October 9, 2015 (for models ≥65,000 Btu/h and <135,000 Btu/h), or October 9, 2016 (for models ≥135,000 Btu/h and <240,000 Btu/h), must meet the applicable minimum energy conservation standard level(s) set forth in this paragraph (e)(1).
Table 9 to Paragraph (
Equipment type | Cooling capacity | Sub-
category | Efficiency level | Compliance date: products
manufactured on and after . . . | Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase | <65,000 Btu/h | AC
HP | EER = 9.0
EER = 9.0 COP = 3.0 | January 1, 2010.
January 1, 2010. | Single package vertical air conditioners and single package vertical heat pumps | ≥65,000 Btu/h and <135,000 Btu/h | AC
HP | EER = 8.9
EER = 8.9 COP = 3.0 | January 1, 2010.
January 1, 2010. | Single package vertical air conditioners and single package vertical heat pumps | ≥135,000 Btu/h and <240,000 Btu/h | AC
HP | EER = 8.6
EER = 8.6 COP = 2.9 | January 1, 2010.
January 1, 2010. |
---|
(2) Each single package vertical air conditioner and single package vertical heat pump manufactured on and after October 9, 2015 (for models ≥65,000 Btu/h and <135,000 Btu/h), or October 9, 2016 (for models ≥135,000 Btu/h and <240,000 Btu/h), but before September 23, 2019, must meet the applicable minimum energy conservation standard level(s) set forth in this paragraph (e)(2).
Table 10 to Paragraph (
Equipment type | Cooling capacity | Sub-
category | Efficiency level | Compliance date: products
manufactured on and after . . . | Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase | <65,000 Btu/h | AC
HP | EER = 9.0
EER = 9.0 COP = 3.0 | January 1, 2010.
January 1, 2010. | Single package vertical air conditioners and single package vertical heat pumps | ≥65,000 Btu/h and <135,000 Btu/h | AC
HP | EER = 10.0
EER = 10.0 COP = 3.0 | October 9, 2015.
October 9, 2015. | Single package vertical air conditioners and single package vertical heat pumps | ≥135,000 Btu/h and <240,000 Btu/h | AC
HP | EER = 10.0
EER = 10.0 COP = 3.0 | October 9, 2016.
October 9, 2016. |
---|
(3) Each single package vertical air conditioner and single package vertical heat pump manufactured on and after September 23, 2019, must meet the applicable minimum energy conservation standard level(s) set forth in this paragraph (e)(3).
Table 11 to Paragraph (
Equipment type | Cooling capacity | Sub-
category | Efficiency level | Compliance date: products
manufactured on and after . . . | Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase | <65,000 Btu/h | AC
HP | EER = 11.0
EER = 11.0 COP = 3.3 | September 23, 2019.
September 23, 2019. | Single package vertical air conditioners and single package vertical heat pumps | ≥65,000 Btu/h and <135,000 Btu/h | AC
HP | EER = 10.0
EER = 10.0 COP = 3.0 | October 9, 2015.
October 9, 2015. | Single package vertical air conditioners and single package vertical heat pumps | ≥135,000 Btu/h and <240,000 Btu/h | AC
HP | EER = 10.0
EER = 10.0 COP = 3.0 | October 9, 2016.
October 9, 2016. |
---|
(f)(1) Each computer room air conditioner with a net sensible cooling capacity less than 65,000 Btu/h manufactured on or after October 29, 2012, and before May 28, 2024 and each computer room air conditioner with a net sensible cooling capacity greater than or equal to 65,000 Btu/h and less than 760,000 Btu/h manufactured on or after October 29, 2013, and before May 28, 2024 must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (f)(1).
Table 12 to Paragraph
Equipment type | Net sensible cooling capacity | Minimum SCOP efficiency | Downflow | Upflow | Air-Cooled | <65,000 Btu/h | 2.20 | 2.09 | ≥65,000 Btu/h and <240,000 Btu/h | 2.10 | 1.99 | ≥240,000 Btu/h and <760,000 Btu/h | 1.90 | 1.79 | Water-Cooled | <65,000 Btu/h | 2.60 | 2.49 | ≥65,000 Btu/h and <240,000 Btu/h | 2.50 | 2.39 | ≥240,000 Btu/h and <760,000 Btu/h | 2.40 | 2.29 | Water-Cooled with Fluid Economizer | <65,000 Btu/h | 2.55 | 2.44 | ≥65,000 Btu/h and <240,000 Btu/h | 2.45 | 2.34 | ≥240,000 Btu/h and <760,000 Btu/h | 2.35 | 2.24 | Glycol-Cooled | <65,000 Btu/h | 2.50 | 2.39 | ≥65,000 Btu/h and <240,000 Btu/h | 2.15 | 2.04 | ≥240,000 Btu/h and <760,000 Btu/h | 2.10 | 1.99 | Glycol-Cooled with Fluid Economizer | <65,000 Btu/h | 2.45 | 2.34 | ≥65,000 Btu/h and <240,000 Btu/h | 2.10 | 1.99 | ≥240,000 Btu/h and <760,000 Btu/h | 2.05 | 1.94 |
---|
(2) Each computer room air conditioner manufactured on or after May 28, 2024, must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (f)(2).
Table 13 to Paragraph
Equipment type | Downflow and upflow ducted | Upflow non-ducted and horizontal flow | Net sensible cooling capacity | Minimum NSenCOP
efficiency | Net sensible cooling capacity | Minimum NSenCOP
efficiency | Downflow | Upflow ducted | Upflow
non-ducted | Horizontal flow | Air-Cooled | <80,000 Btu/h | 2.70 | 2.67 | <65,000 Btu/h | 2.16 | 2.65 | ≥80,000 Btu/h and <295,000 Btu/h | 2.58 | 2.55 | ≥65,000 Btu/h and <240,000 Btu/h | 2.04 | 2.55 | ≥295,000 Btu/h and <930,000 Btu/h | 2.36 | 2.33 | ≥240,000 Btu/h and <760,000 Btu/h | 1.89 | 2.47 | Air-Cooled with Fluid Economizer | <80,000 Btu/h
≥80,000 Btu/h and <295,000 Btu/h | 2.70
2.58 | 2.67
2.55 | <65,000 Btu/h
≥65,000 Btu/h and <240,000 Btu/h | 2.09
1.99 | 2.65
2.55 | ≥295,000 Btu/h and <930,000 Btu/h | 2.36 | 2.33 | ≥240,000 Btu/h and <760,000 Btu/h | 1.81 | 2.47 | Water-Cooled | <80,000 Btu/h | 2.82 | 2.79 | <65,000 Btu/h | 2.43 | 2.79 | ≥80,000 Btu/h and <295,000 Btu/h | 2.73 | 2.70 | ≥65,000 Btu/h and <240,000 Btu/h | 2.32 | 2.68 | ≥295,000 Btu/h and <930,000 Btu/h | 2.67 | 2.64 | ≥240,000 Btu/h and <760,000 Btu/h | 2.20 | 2.60 | Water-Cooled with Fluid Economizer | <80,000 Btu/h
≥80,000 Btu/h and <295,000 Btu/h | 2.77
2.68 | 2.74
2.65 | <65,000 Btu/h
≥65,000 Btu/h and <240,000 Btu/h | 2.35
2.24 | 2.71
2.60 | ≥295,000 Btu/h and <930,000 Btu/h | 2.61 | 2.58 | ≥240,000 Btu/h and <760,000 Btu/h | 2.12 | 2.54 | Glycol-Cooled | <80,000 Btu/h | 2.56 | 2.53 | <65,000 Btu/h | 2.08 | 2.48 | ≥80,000 Btu/h and <295,000 Btu/h | 2.24 | 2.21 | ≥65,000 Btu/h and <240,000 Btu/h | 1.90 | 2.18 | ≥295,000 Btu/h and <930,000 Btu/h | 2.21 | 2.18 | ≥240,000 Btu/h and <760,000 Btu/h | 1.81 | 2.18 | Glycol-Cooled with Fluid Economizer | <80,000 Btu/h
≥80,000 Btu/h and <295,000 Btu/h | 2.51
2.19 | 2.48
2.16 | <65,000 Btu/h
≥65,000 Btu/h and <240,000 Btu/h | 2.00
1.82 | 2.44
2.10 | ≥295,000 Btu/h and <930,000 Btu/h | 2.15 | 2.12 | ≥240,000 Btu/h and <760,000 Btu/h | 1.73 | 2.10 |
---|
Table 14 to Paragraph
Equipment type | Net sensible cooling capacity | Minimum NSenCOP
efficiency | Ducted | Non-ducted | Air-Cooled with Free Air Discharge Condenser | <29,000 Btu/h | 2.05 | 2.08 | ≥29,000 Btu/h and <65,000 Btu/h | 2.02 | 2.05 | ≥65,000 Btu/h and <760,000 Btu/h | 1.92 | 1.94 | Air-Cooled with Free Air Discharge Condenser and Fluid Economizer | <29,000 Btu/h | 2.01 | 2.04 | ≥29,000 Btu/h and <65,000 Btu/h | 1.97 | 2 | ≥65,000 Btu/h and <760,000 Btu/h | 1.87 | 1.89 | Air-Cooled with Ducted Condenser | <29,000 Btu/h | 1.86 | 1.89 | ≥29,000 Btu/h and <65,000 Btu/h | 1.83 | 1.86 | ≥65,000 Btu/h and <760,000 Btu/h | 1.73 | 1.75 | Air-Cooled with Fluid Economizer and Ducted Condenser | <29,000 Btu/h | 1.82 | 1.85 | ≥29,000 Btu/h and <65,000 Btu/h | 1.78 | 1.81 | ≥65,000 Btu/h and <760,000 Btu/h | 1.68 | 1.7 | Water-Cooled | <29,000 Btu/h | 2.38 | 2.41 | ≥29,000 Btu/h and <65,000 Btu/h | 2.28 | 2.31 | ≥65,000 Btu/h and <760,000 Btu/h | 2.18 | 2.2 | Water-Cooled with Fluid Economizer | <29,000 Btu/h | 2.33 | 2.36 | ≥29,000 Btu/h and <65,000 Btu/h | 2.23 | 2.26 | ≥65,000 Btu/h and <760,000 Btu/h | 2.13 | 2.16 | Glycol-Cooled | <29,000 Btu/h | 1.97 | 2 | ≥29,000 Btu/h and <65,000 Btu/h | 1.93 | 1.98 | ≥65,000 Btu/h and <760,000 Btu/h | 1.78 | 1.81 | Glycol-Cooled with Fluid Economizer | <29,000 Btu/h | 1.92 | 1.95 | ≥29,000 Btu/h and <65,000 Btu/h | 1.88 | 1.93 | ≥65,000 Btu/h and <760,000 Btu/h | 1.73 | 1.76 |
---|
(g)(1) Each variable refrigerant flow air conditioner or heat pump manufactured on or after the compliance date listed in table 15 to this paragraph (g)(1) and prior to January 1, 2024, must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (g)(1).
Table 15 to Paragraph (
Equipment type | Cooling
capacity | Heating type 1 | Efficiency level | Compliance date: equipment
manufactured on and after . . . | VRF Multi-Split Air Conditioners (Air-Cooled) | ≥65,000 Btu/h and <135,000 Btu/h | No Heating or Electric Resistance Heating | 11.2 EER | January 1, 2010. | All Other Types of Heating | 11.0 EER | January 1, 2010. | ≥135,000 Btu/h and <240,000 Btu/h | No Heating or Electric Resistance Heating | 11.0 EER | January 1, 2010. | All Other Types of Heating | 10.8 EER | January 1, 2010. | ≥240,000 Btu/h and <760,000 Btu/h | No Heating or Electric Resistance Heating | 10.0 EER | January 1, 2010. | All Other Types of Heating | 9.8 EER | January 1, 2010. | VRF Multi-Split Heat Pumps (Air-Cooled) | ≥65,000 Btu/h and <135,000 Btu/h | No Heating or Electric Resistance Heating | 11.0 EER, 3.3 COP | January 1, 2010. | All Other Types of Heating | 10.8 EER, 3.3 COP | January 1, 2010. | ≥135,000 Btu/h and <240,000 Btu/h | No Heating or Electric Resistance Heating | 10.6 EER, 3.2 COP | January 1, 2010. | All Other Types of Heating | 10.4 EER, 3.2 COP | January 1, 2010. | ≥240,000 Btu/h and <760,000 Btu/h | No Heating or Electric Resistance Heating | 9.5 EER, 3.2 COP | January 1, 2010. | All Other Types of Heating | 9.3 EER, 3.2 COP | January 1, 2010. | VRF Multi-Split Heat Pumps (Water-Source) | <17,000 Btu/h | Without Heat Recovery | 12.0 EER,
4.2 COP | October 29, 2012.
October 29, 2003. | With Heat Recovery | 11.8 EER
4.2 COP | October 29, 2012.
October 29, 2003. | ≥17,000 Btu/h and <65,000 Btu/h | All | 12.0 EER, 4.2 COP | October 29, 2003. | ≥65,000 Btu/h and <135,000 Btu/h | All | 12.0 EER, 4.2 COP | October 29, 2003. | ≥135,000 Btu/h and <760,000 Btu/h | Without Heat Recovery | 10.0 EER, 3.9 COP | October 29, 2013. | With Heat Recovery | 9.8 EER, 3.9 COP | October 29, 2013. |
---|
1 VRF multi-split heat pumps (air-cooled) with heat recovery fall under the category of “All Other Types of Heating” unless they also have electric resistance heating, in which case it falls under the category for “No Heating or Electric Resistance Heating.”
(2) Each variable refrigerant flow air conditioner or heat pump (except air-cooled systems with cooling capacity less than 65,000 Btu/h) manufactured on or after January 1, 2024, must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (g)(2).
Table 16 to Paragraph (
Equipment type | Size category | Heating type | Minimum efficiency | VRF Multi-Split Air Conditioners (Air-Cooled) | ≥65,000 and <135,000 Btu/h | All | 15.5 IEER. | ≥135,000 and <240,000 Btu/h | All | 14.9 IEER. | ≥240,000 Btu/h and <760,000 Btu/h | All | 13.9 IEER. | VRF Multi-Split Heat Pumps (Air-Cooled) | ≥65,000 and <135,000 Btu/h | Heat Pump without Heat Recovery | 14.6 IEER, 3.3 COP. | Heat Pump with Heat Recovery | 14.4 IEER, 3.3 COP. | ≥135,000 and <240,000 Btu/h | Heat Pump without Heat Recovery
Heat Pump with Heat Recovery | 13.9 IEER, 3.2 COP.
13.7 IEER, 3.2 COP. | ≥240,000 Btu/h and <760,000 Btu/h | Heat Pump without Heat Recovery
Heat Pump with Heat Recovery | 12.7 IEER, 3.2 COP.
12.5 IEER, 3.2 COP. | VRF Multi-Split Heat Pumps (Water-Source) | <65,000 Btu/h | Heat Pump without Heat Recovery
Heat Pump with Heat Recovery | 16.0 IEER, 4.3 COP.
15.8 IEER, 4.3 COP. | ≥65,000 and <135,000 Btu/h | Heat Pump without Heat Recovery
Heat Pump with Heat Recovery | 16.0 IEER, 4.3 COP.
15.8 IEER, 4.3 COP. | ≥135,000 and <240,000 Btu/h | Heat Pump without Heat Recovery
Heat Pump with Heat Recovery | 14.0 IEER, 4.0 COP.
13.8 IEER, 4.0 COP. | ≥240,000 Btu/h and <760,000 Btu/h | Heat Pump without Heat Recovery
Heat Pump with Heat Recovery | 12.0 IEER, 3.9 COP.
11.8 IEER, 3.9 COP. |
---|
(h) Each direct expansion-dedicated outdoor air system manufactured on or after the compliance date listed in table 17 to this paragraph (h) must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (h).
Table 17 to Paragraph (
Equipment
category | Subcategory | Efficiency level | Compliance date: equipment manufactured starting on . . . | Direct expansion-dedicated outdoor air systems | (AC)—Air-cooled without ventilation energy recovery systems | ISMRE2 = 3.8 | May 1, 2024. | (AC w/VERS)—Air-cooled with ventilation energy recovery systems | ISMRE2 = 5.0 | May 1, 2024. | (ASHP)—Air-source heat pumps without ventilation energy recovery systems | ISMRE2 = 3.8
ISCOP2 = 2.05 | May 1, 2024. | (ASHP w/VERS)—Air-source heat pumps with ventilation energy recovery systems | ISMRE2 = 5.0
ISCOP2 = 3.20 | May 1, 2024. | (WC)—Water-cooled without ventilation energy recovery systems | ISMRE2 = 4.7 | May 1, 2024. | (WC w/VERS)—Water-cooled with ventilation energy recovery systems | ISMRE2 = 5.1 | May 1, 2024. | (WSHP)—Water-source heat pumps without ventilation energy recovery systems | ISMRE2 = 3.8
ISCOP2 = 2.13 | May 1, 2024. | (WSHP w/VERS)—Water-source heat pumps with ventilation energy recovery systems | ISMRE2 = 4.6
ISCOP2 = 4.04 | May 1, 2024. |
---|
(i) Air-cooled, three-phase, commercial package air conditioning and heating equipment with a cooling capacity of less than 65,000 Btu/h and air-cooled, three-phase variable refrigerant flow multi-split air conditioning and heating equipment with a cooling capacity of less than 65,000 Btu/h manufactured on or after the compliance date listed in tables 18 and 19 to this paragraph (i) must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (i).
Table 18 to Paragraph (
Equipment type | Cooling
capacity | Subcategory | Minimum efficiency | Compliance date: equipment
manufactured starting on . . . | Commercial Package Air Conditioning Equipment | <65,000 Btu/h | Split-System | 13.0 SEER | June 16, 2008. 1 | Commercial Package Air Conditioning Equipment | <65,000 Btu/h | Single-Package | 14.0 SEER | January 1, 2017. 1 | Commercial Package Air Conditioning and Heating Equipment | <65,000 Btu/h | Split-System | 14.0 SEER
8.2 HSPF | January 1, 2017. 1 | Commercial Package Air Conditioning and Heating Equipment | <65,000 Btu/h | Single-Package | 14.0 SEER
8.0 HSPF | January 1, 2017. 1 | VRF Air Conditioners | <65,000 Btu/h | 13.0 SEER | June 16, 2008. 1 | VRF Heat Pumps | <65,000 Btu/h | 13.0 SEER
7.7 HSPF | June 16, 2008. 1 |
---|
1 And manufactured before January 1, 2025. For equipment manufactured on or after January 1, 2025, see table 19 to this paragraph (i) for updated efficiency standards.
Table 19 to Paragraph (
Equipment type | Cooling
capacity | Subcategory | Minimum efficiency | Compliance date: equipment
manufactured starting on . . . | Commercial Package Air Conditioning Equipment | <65,000 Btu/h | Split-System | 13.4 SEER2 | January 1, 2025. | Commercial Package Air Conditioning Equipment | <65,000 Btu/h | Single-Package | 13.4 SEER2 | January 1, 2025. | Commercial Package Air Conditioning and Heating Equipment | <65,000 Btu/h | Split-System | 14.3 SEER2
7.5 HSPF2 | January 1, 2025. | Commercial Package Air Conditioning and Heating Equipment | <65,000 Btu/h | Single-Package | 13.4 SEER2
6.7 HSPF2 | January 1, 2025. | Space-Constrained Commercial Package Air Conditioning Equipment | ≤30,000 Btu/h | Split-System | 12.7 SEER2 | January 1, 2025. | Space-Constrained Commercial Package Air Conditioning Equipment | ≤30,000 Btu/h | Single-Package | 13.9 SEER2 | January 1, 2025. | Space-Constrained Commercial Package Air Conditioning and Heating Equipment | ≤30,000 Btu/h | Split-System | 13.9 SEER2
7.0 HSPF2 | January 1, 2025. | Space-Constrained Commercial Package Air Conditioning and Heating Equipment | ≤30,000 Btu/h | Single-Package | 13.9 SEER2
6.7 HSPF2 | January 1, 2025. | Small-Duct, High-Velocity Commercial Package Air Conditioning | <65,000 Btu/h | Split-System | 13.0 SEER2 | January 1, 2025. | Small-Duct, High-Velocity Commercial Package Air Conditioning and Heating Equipment | <65,000 Btu/h | Split-System | 14.0 SEER2
6.9 HSPF2 | January 1, 2025. | VRF Air Conditioners | <65,000 Btu/h | 13.4 SEER2 | January 1, 2025. | VRF Heat Pumps | <65,000 Btu/h | 13.4 SEER2
7.5 HSPF2 | January 1, 2025. |
---|