Appendix O - Appendix O to Subpart B of Part 430—Uniform Test Method for Measuring the Energy Consumption of Vented Home Heating Equipment
Prior to November 16, 2022, representations with respect to the energy use or efficiency of vented home heating equipment, including compliance certifications, must be based on testing conducted in accordance with either this appendix as it now appears or appendix O as it appeared at 10 Cspan part 430, subpart B revised as of January 1, 2021.
On and after November 16, 2022, representations with respect to energy use or efficiency of vented home heating equipment, including compliance certifications, must be based on testing conducted in accordance with this appendix.
0.0 Incorporation by Reference.DOE incorporated by reference in § 430.3: ANSI Z21.86-2016; ASHRAE 103-2017; ASTM D2156-09 (R2018); IEC 62301; UL 729-2016; UL 730-2016; and UL 896-2016 in their entirety. However, only enumerated provisions of ANSI Z21.86-2016; ASHRAE 103-2017, UL 729-2016, UL 730-2016, and UL 896-2016 are applicable to this appendix, as follows:
0.1 ANSI Z21.86-2016
(i) Section 5.2—Test gases
(ii) Section 9.1.3
(iii) Section 11.1.3
(iv) Section 11.7—Temperature at discharge air opening and surface temperatures
0.2 ASHRAE 103-2017
(i) Section 6—INSTRUMENTS
(ii) Section 8.2.2.3.1—Oil Supply
(iii) Section 8.6—Jacket Loss Measurement
(iv) Section 8.8.3—Additional Optional Method of Testing for Determining DP and DF for Furnaces and Boilers
(v) Section 9.10—Optional Test Procedures for Condensing Furnaces and Boilers that Have no OFF-Period Flue Losses
0.3 UL 729-2016
(i) Section 38.1—Enclosure
(ii) Section 38.2—Chimney connector
0.4 UL 730-2016
(i) Section 36.1—Enclosure
(ii) Section 36.2—Chimney connector
(iii) Sections 37.5.8 through 37.5.180.5 UL 896-2016
(i) Section 37.1.2
(ii) Section 37.1.3
1.0 Definitions1.1 “Active mode” means the condition during the heating season in which the vented heater is connected to the power source, and either the burner or any electrical auxiliary is activated.
1.2 “Air shutter” means an adjustable device for varying the size of the primary air inlet(s) to the combustion chamber power burner.
1.3 “Air tube” means a tube which carries combustion air from the burner fan to the burner nozzle for combustion.
1.4 “Barometic draft regulator or barometric damper” means a mechanical device designed to maintain a constant draft in a vented heater.
1.5 “Condensing vented heater” means a vented heater that, during the laboratory tests prescribed in this appendix, condenses part of the water vapor in the flue gases.
1.6 “Draft hood” means an external device which performs the same function as an integral draft diverter, as defined in section 1.17 of this appendix.
1.7 “Electro-mechanical stack damper” means a type of stack damper which is operated by electrical and/or mechanical means.
1.8 “Excess air” means air which passes through the combustion chamber and the vented heater flues in excess of that which is theoretically required for complete combustion.
1.9 “Flue” means a conduit between the flue outlet of a vented heater and the integral draft diverter, draft hood, barometric damper or vent terminal through which the flue gases pass prior to the point of draft relief.
1.10 “Flue damper” means a device installed between the furnace and the integral draft diverter, draft hood, barometric draft regulator, or vent terminal which is not equipped with a draft control device, designed to open the venting system when the appliance is in operation and to close the venting system when the appliance is in a standby condition.
1.11 “Flue gases” means reaction products resulting from the combustion of a fuel with the oxygen of the air, including the inerts and any excess air.
1.12 “Flue losses” means the sum of sensible and latent heat losses above room temperature of the flue gases leaving a vented heater.
1.13 “Flue outlet” means the opening provided in a vented heater for the exhaust of the flue gases from the combustion chamber.
1.14 “Heat input” (Q
1.15 “Heating capacity” (Q
1.16 “Higher heating value” (HHV) means the heat produced per unit of fuel when complete combustion takes place at constant pressure and the products of combustion are cooled to the initial temperature of the fuel and air and when the water vapor formed during combustion is condensed. The higher heating value is usually expressed in Btu's per pound, Btu's per cubic foot for gaseous fuel, or Btu's per gallon for liquid fuel.
1.17 “IEC 62301 (Second Edition)” means the test standard published by the International Electrotechnical Commission, titled “Household electrical appliances—Measurement of standby power,” Publication 62301 Edition 2.0 2011-01 (incorporated by reference; see § 430.3).
1.18 “Induced draft” means a method of drawing air into the combustion chamber by mechanical means.
1.19 “Infiltration parameter” means that portion of unconditioned outside air drawn into the heated space as a consequence of loss of conditioned air through the exhaust system of a vented heater.
1.20 “Integral draft diverter” means a device which is an integral part of a vented heater, designed to: (1) Provide for the exhaust of the products of combustion in the event of no draft, back draft, or stoppage beyond the draft diverter, (2) prevent a back draft from entering the vented heater, and (3) neutralize the stack action of the chimney or gas vent upon the operation of the vented heater.
1.21 “Manually controlled vented heaters” means either gas or oil fueled vented heaters equipped without thermostats.
1.22 “Modulating control” means either a step-modulating or two-stage control.
1.23 “Off mode” means the condition during the non-heating season in which the vented heater is connected to the power source, and neither the burner nor any electrical auxiliary is activated.
1.24 “Power burner” means a vented heater burner which supplies air for combustion at a pressure exceeding atmospheric pressure, or a burner which depends on the draft induced by a fan incorporated in the furnace for proper operation.
1.25 “Reduced heat input rate” means the factory adjusted lowest reduced heat input rate for vented home heating equipment equipped with either two stage thermostats or step-modulating thermostats.
1.26 “Seasonal off switch” means the control device, such as a lever or toggle, on the vented heater that affects a difference in off mode energy consumption as compared to standby mode consumption.
1.27 “Single-stage thermostat” means a thermostat that cycles a burner at the maximum heat input rate and off.
1.28 “Stack” means the portion of the exhaust system downstream of the integral draft diverter, draft hood or barometric draft regulator.
1.29 “Stack damper” means a device installed downstream of the integral draft diverter, draft hood, or barometric draft regulator, designed to open the venting system when the appliance is in operation and to close off the venting system when the appliance is in the standby condition.
1.30 “Stack gases” means the flue gases combined with dilution air that enters at the integral draft diverter, draft hood or barometric draft regulator.
1.31 “Standby mode” means the condition during the heating season in which the vented heater is connected to the power source, and neither the burner nor any electrical auxiliary is activated.
1.32 “Steady-state conditions for vented home heating equipment” means equilibrium conditions as indicated by temperature variations of not more than 5 °F (2.8C) in the flue gas temperature for units equipped with draft hoods, barometric draft regulators or direct vent systems, in three successive readings taken 15 minutes apart or not more than 3 °F (1.7C) in the stack gas temperature for units equipped with integral draft diverters in three successive readings taken 15 minutes apart.
1.33 “Step-modulating control” means a control that either cycles off and on at the low input if the heating load is light, or gradually, increases the heat input to meet any higher heating load that cannot be met with the low firing rate.
1.34 “Thermal stack damper” means a type of stack damper which is dependent for operation exclusively upon the direct conversion of thermal energy of the stack gases into movement of the damper plate.
1.35 “Two stage control” means a control that either cycles a burner at the reduced heat input rate and off or cycles a burner at the maximum heat input rate and off.
1.36 “Vaporizing-type oil burner” means a device with an oil vaporizing bowl or other receptacle designed to operate by vaporizing liquid fuel oil by the heat of combustion and mixing the vaporized fuel with air.
1.37 “Vent/air intake terminal” means a device which is located on the outside of a building and is connected to a vented heater by a system of conduits. It is composed of an air intake terminal through which the air for combustion is taken from the outside atmosphere and a vent terminal from which flue gases are discharged.
1.38 “Vent limiter” means a device which limits the flow of air from the atmospheric diaphragm chamber of a gas pressure regulator to the atmosphere. A vent limiter may be a limiting orifice or other limiting device.
1.39 “Vent pipe” means the passages and conduits in a direct vent system through which gases pass from the combustion chamber to the outdoor air.
2.0 Testing conditions.2.1 Installation of test unit.
2.1.1 Vented wall furnaces (including direct vent systems). Install non-direct vent gas fueled vented wall furnaces as specified in Section 11.1.3 of ANSI Z21.86-2016. Install direct vent gas fueled vented wall furnaces as specified in Section 9.1.3 of ANSI Z21.86-2016. Install oil-fueled vented wall furnaces as specified in Section 36.1 of UL 730-2016.
2.1.2 Vented floor furnaces. Install vented floor furnaces for test as specified in Section 38.1 of UL 729-2016.
2.1.3 Vented room heaters. Install vented room heaters for test in accordance with the manufacturer's installation and operations (I&O) manual provided with the unit.
2.2 Flue and stack requirements.
2.2.1 Gas fueled vented home heating equipment employing integral draft diverters and draft hoods (excluding direct vent systems). Attach to, and vertically above the outlet of gas-fueled vented home heating equipment employing draft diverters or draft hoods with vertically discharging outlets, a five (5) foot long test stack having a cross-sectional area the same size as the draft diverter outlet.
Attach to the outlet of vented heaters having a horizontally discharging draft diverter or draft hood outlet a 90-degree elbow, and a five (5) foot long vertical test stack. A horizontal section of pipe may be used on the floor furnace between the diverter and the elbow, if necessary, to clear any framing used in the installation. Use the minimum length of pipe possible for this section. Use stack, elbow, and horizontal section with same cross-sectional area as the diverter outlet.
2.2 Oil-fueled vented home heating equipment (excluding direct vent systems). Use flue connections for oil-fueled vented floor furnaces as specified in Section 38.2 of UL 729-2016, Section 36.2 of UL 730-2016 for oil-fueled vented wall furnaces, and Sections 37.1.2 and 37.1.3 of UL 896-2016 for oil-fueled vented room heaters.
2.2.3 Direct vent systems. Have the exhaust/air intake system supplied by the manufacturer in place during all tests. Test units intended for installation with a variety of vent pipe lengths with the minimum length recommended by the manufacturer in the I&O manual. Do not connect a heater employing a direct vent system to a chimney or induced draft source. Vent the gas solely on the provision for venting incorporated in the heater and the vent/air intake system supplied with it.
2.2.4 Condensing vented heater, additional flue requirements. The flue pipe installation must not allow condensate formed in the flue pipe to flow back into the unit. An initial downward slope from the unit's exit, an offset with a drip leg, annular collection rings, or drain holes must be included in the flue pipe installation without disturbing normal flue gas flow. Flue gases should not flow out of the drain with the condensate. For condensing vented heaters that do not include means for collection of condensate, a means to collect condensate must be supplied by the test lab for the purposes of testing.
2.3 Fuel supply.
2.3.1 Natural gas. For a gas-fueled vented heater, maintain the gas supply to the unit under test at an inlet test pressure immediately ahead of all controls at 7 to 10 inches water column. If the heater is equipped with a gas pressure regulator, maintain the regulator outlet pressure within the greater of ±0.2 inches water column, or ±10 percent, of the manufacturer-specified manifold pressure on the nameplate of the unit or in the I&O manual. Use natural gas having a specific gravity between 0.57 and 0.70 and a higher heating value within ±5 percent of 1,025 Btu per standard cubic foot. Determine the actual higher heating value in Btu per standard cubic foot for the natural gas to be used in the test with an error no greater than one percent. If the burner cannot be adjusted to obtain a heat input rate of within ±2 percent of the hourly Btu rating specified by the manufacturer on the nameplate of the unit or in the I&O manual, as required by section 2.4.1 of this appendix, maintain the gas supply to the unit under test at an inlet test pressure immediately ahead of all controls at any value within the range specified on the nameplate of the unit or in the I&O manual that results in a heat input rate of within ±2 percent of the hourly Btu rating specified by the manufacturer on the nameplate of the unit or in the I&O manual.
2.3.2 Propane gas. For a propane-gas-fueled vented heater, maintain the gas supply to the unit under test at an inlet pressure of 11 to 13 inches water column. If the heater is equipped with a gas pressure regulator, maintain the regulator outlet pressure within the greater of ±0.2 inches water column, or ±10 percent, of the manufacturer's specified manifold pressure on the nameplate of the unit or in the I&O manual. Use propane having a specific gravity between 1.522 and 1.574 and a higher heating value within ±5 percent of 2,500 Btu per standard cubic foot. Determine the actual higher heating value in Btu per standard cubic foot for the propane to be used in the test. If the burner cannot be adjusted to obtain a heat input rate of within ±2 percent of the hourly Btu rating specified by the manufacturer on the nameplate of the unit or in the I&O manual, as required by section 2.4.1 of this appendix, maintain the gas supply to the unit under test at an inlet test pressure immediately ahead of all controls at any value within the range specified on the nameplate of the unit or in the I&O manual that results in a heat input rate of within ±2 percent of the hourly Btu rating specified by the manufacturer on the nameplate of the unit or in the I&O manual.
2.3.3 Other test gas. For vented heaters fueled by other test gases, use test gases with characteristics as described in Table 3 of Section 5.2 of ANSI Z21.86-2016. Use gases with a measured higher heating value within ±5 percent of the values specified in Table 3 of Section 5.2 of ANSI Z21.86-2016. Determine the actual higher heating value of the gas used in the test with an error no greater than one percent.
2.3.4 Oil supply. For an oil-fueled vented heater, use No. 1 fuel oil (kerosene) for vaporizing-type burners and either No. 1 or No. 2 fuel oil, as specified by the manufacturer in the I&O manual provided with the unit, for mechanical atomizing type burners. Use test fuel conforming to the specifications given in Tables 2 and 3 of Section 8.2.2.3.1 of ASHRAE 103-2017. Measure the higher heating value of the test fuel within ±1 percent.
2.3.5 Electrical supply. For auxiliary electric components of a vented heater, maintain the electrical supply to the test unit within ±1 percent of the nameplate voltage for the entire test cycle. If a voltage range is used for nameplate voltage, maintain the electrical supply within ±1 percent of the mid-point of the nameplate voltage range.
2.4 Burner adjustments.
2.4.1 Gas burner adjustments. Adjust the burners of gas-fueled vented heaters to their maximum Btu ratings at the test pressure specified in section 2.3 of this appendix. Correct the burner volumetric flow rate to 60 °F (15.6 °C) and 30 inches of mercury barometric pressure, set the fuel flow rate to obtain a heat rate of within ±2 percent of the hourly Btu rating specified by the manufacturer on the nameplate of the unit or in the I&O manual, as measured after 15 minutes of operation, starting with all parts of the vented heater at room temperature. Set the primary air shutters in accordance with the manufacturer's recommendations on the nameplate of the unit or in the I&O manual to give a good flame at this adjustment. Do not allow the deposit of carbon during any test specified herein. If a vent limiting means is provided on a gas pressure regulator, have it in place during all tests.
For gas-fueled heaters with modulating controls, adjust the controls to operate the heater at the maximum fuel input rate. Set the thermostat control to the maximum setting. Start the heater by turning the safety control valve to the “on” position. In order to prevent modulation of the burner at maximum input, place the thermostat sensing element in a temperature control bath which is held at a temperature below the maximum set point temperature of the control.
For gas-fueled heaters with modulating controls, adjust the controls to operate the heater at the reduced fuel input rate. Set the thermostat control to the minimum setting. Start the heater by turning the safety control valve to the “on” position. If ambient test room temperature is above the lowest control set point temperature, initiate burner operation by placing the thermostat sensing element in a temperature control bath that is held at a temperature below the minimum set point temperature of the control.
2.4.2 Oil burner adjustments. Adjust the burners of oil-fueled vented heaters to give the CO
2.5 Circulating air adjustments.
2.5.1 Forced-air vented wall furnaces (including direct vent systems). During testing, maintain the air flow through the heater as specified by the manufacturer in the I&O manual provided with the unit and operate the vented heater with the outlet air temperature between 80 °F and 130 °F above room temperature. If adjustable air discharge registers are provided, adjust them so as to provide the maximum possible air restriction. Measure air discharge temperature as specified in Section 11.7.2 of ANSI Z21.86-2016.
2.5.2 Fan-type vented room heaters and floor furnaces. During tests on fan-type furnaces and heaters, adjust the air flow through the heater as specified by the manufacturer. If adjustable air discharge registers are provided, adjust them to provide the maximum possible air restriction.
2.6 Location of temperature measuring instrumentation.
2.6.1 Gas-fueled vented home heating equipment (including direct vent systems). Install thermocouples for measuring the heated air temperature as described in Section 11.7.5 of ANSI Z21.86-2016. Establish the temperature of the inlet air by means of a single No. 24 AWG bead-type thermocouple located in the center of the plane of each inlet air opening. Use bead-type thermocouples having wire size not greater than No. 24 American Wire Gauge (AWG). If a thermocouple has a direct line of sight with the fire, install a radiation shield, meeting the material and minimum thickness requirements from Section 8.14.1 of ANSI Z21.86-2016, on the fire side of the thermocouple only, and position the shield so that it does not touch the thermocouple junction.
2.6.1.1 Integral draft diverter. For units employing an integral draft diverter, install nine thermocouples, wired in parallel, in a horizontal plane in the five-foot test stack located one foot from the test stack inlet. Equalize the length of all thermocouple leads before paralleling. Locate one thermocouple in the center of the stack. Locate eight thermocouples along imaginary lines intersecting at right angles in this horizontal plane at points one third and two thirds of the distance between the center of the stack and the stack wall.
For units with a stack diameter 2 inches or less, five thermocouples may be installed instead of nine. Locate one thermocouple in the center of the stack. Locate four thermocouples along imaginary lines intersecting at right angles in this horizontal plane at points halfway between the center of the stack and the stack wall.
2.6.1.2 Direct vent system. For units which employ a direct vent system, locate at least one thermocouple at the center of each flue way exiting the heat exchanger. Provide radiation shields if the thermocouples are exposed to burner radiation.
2.6.1.3 Draft hood or direct vent system which does not intentionally preheat incoming air. For units which employ a draft hood or units which employ a direct vent system which does not intentionally preheat the incoming combustion air, such as a non-concentric direct vent system, install nine thermocouples, wired in parallel, in a horizontal plane located within 12 inches (304.8 mm) of the heater outlet and upstream of the draft hood on units so equipped. Locate one thermocouple in the center of the pipe and eight thermocouples along imaginary lines intersecting at right angles in this horizontal plane at points one third and two thirds of the distance between the center of the pipe and the pipe wall.
For units with a flue pipe diameter of 2 inches or less, five thermocouples may be installed instead of nine. Locate one thermocouple in the center of the pipe and four thermocouples along imaginary lines intersecting at right angles in this horizontal plane at points halfway between the center of the pipe and the pipe wall.
2.6.1.4 Direct vent system which intentionally preheat incoming air. For units which employ direct vent systems that intentionally preheat the incoming combustion air, such as a concentric direct vent system, install nine thermocouples, wired in parallel, in a plane parallel to and located within 6 inches (152.4 mm) of the vent/air intake terminal. Equalize the length of all thermocouple leads before paralleling. Locate one thermocouple in the center of the flue pipe and eight thermocouples along imaginary lines intersecting at right angles in this plane at points one third and two thirds of the distance between the center of the flue pipe and the pipe wall.
For units with a flue pipe diameter of 2 inches or less, five thermocouples may be installed instead of nine. Locate one thermocouple in the center of the flue pipe and four thermocouples along imaginary lines intersecting at right angles in this plane at points halfway between the center of the flue pipe and the pipe wall.
2.6.2 Oil-fueled vented home heating equipment (including direct vent systems).
Install thermocouples for measuring the heated air temperature as described in Sections 37.5.8 through 37.5.18 of UL 730-2016. Establish the temperature of the inlet air by means of a single No. 24 AWG bead-type thermocouple located in the center of the plane of each inlet air opening. Use bead-type thermocouples having a wire size not greater than No. 24 AWG. If there is a thermocouple that has a direct line of sight with the fire, install a radiation shield, meeting the material and minimum thickness requirements from Section 8.14.1 of ANSI Z21.86-2016, on the fire side of the thermocouple only, and position the shield so that it does not touch the thermocouple junction.
Install nine thermocouples, wired in parallel and having equal length leads, in a plane perpendicular to the axis of the flue pipe. Locate this plane at the position shown in Figure 36.4 of UL 730-2016, or Figure 38.1 and 38.2 of UL 729-2016 for a single thermocouple, except that on direct vent systems which intentionally preheat the incoming combustion air, locate this plane within 6 inches (152.5 mm) of the outlet of the vent/air intake terminal. Locate one thermocouple in the center of the flue pipe and eight thermocouples along imaginary lines intersecting at right angles in this plane at points one third and two thirds of the distance between the center of the pipe and pipe wall.
For units with a flue pipe diameter of 2 inches or less, five thermocouples may be installed instead of nine. Wire the thermocouples in parallel with equal length leads, in a plane perpendicular to the axis of the flue pipe. Locate this plane at the position shown in Figure 36.4 of UL 730-2016, or Figure 38.1 and 38.2 of UL 729-2016 for a single thermocouple, except that on direct vent systems which intentionally preheat the incoming combustion air, locate this plane within 6 inches (152.5 mm) of the outlet of the vent/air intake terminal. Locate one thermocouple in the center of the flue pipe and four thermocouples along imaginary lines intersecting at right angles in this plane at points halfway between the center of the pipe and pipe wall.
2.7 Combustion measurement instrumentation. Analyze the samples of stack and flue gases for vented heaters to determine the concentration by volume of carbon dioxide present in the dry gas with instrumentation which will result in a reading having an accuracy of ±0.1 percentage point.
2.8 Energy flow instrumentation. Install one or more instruments, which measure the rate of gas flow or fuel oil supplied to the vented heater, and if appropriate, the electrical energy with an error no greater than one percent.
2.9 Room ambient temperature. The room ambient temperature shall be the arithmetic average temperature of the test area, determined by measurement with four No. 24 AWG bead-type thermocouples with junctions shielded against radiation using shielding meeting the material and minimum thickness requirements from Section 8.14.1 of ANSI Z21.86-2016, located approximately at 90-degree positions on a circle circumscribing the heater or heater enclosure under test, in a horizontal plane approximately at the vertical midpoint of the appliance or test enclosure, and with the junctions approximately 24 inches from sides of the heater or test enclosure and located so as not to be affected by other than room air.
The value T
Locate a thermocouple at each elevation of draft relief inlet opening and combustion air inlet opening at a distance of approximately 24 inches from the inlet openings. The temperature of the air for combustion and the air for draft relief shall not differ more than ±5 °F from the room ambient temperature as measured above at any point in time. This requirement for combustion air inlet temperature does not need to be met once the burner is shut off during the testing described in sections 3.3 and 3.6 of this appendix.
2.10 Equipment used to measure mass flow rate in flue and stack. The tracer gas chosen for this task should have a density which is less than or approximately equal to the density of air. Use a gas unreactive with the environment to be encountered. Using instrumentation of either the batch or continuous type, measure the concentration of tracer gas with an error no greater than 2 percent of the value of the concentration measured.
2.11 Equipment with multiple control modes.
2.11.1 For equipment that has both manual and automatic thermostat control modes, test the unit according to the procedure for its automatic control mode, i.e., single-stage, two-stage, or step-modulating.
2.11.2 For equipment that has multiple automatic thermostat control modes, test in the default mode (or similarly named mode identified for normal operation) as defined by the manufacturer in its I&O manual. If a default mode is not defined in the I&O manual, test in the mode in which the equipment operates as shipped from the manufacturer.
3.0 Testing and measurements.3.1 Steady-state testing.
3.1.1 Gas fueled vented home heating equipment (including direct vent systems). Set up the vented heater as specified in sections 2.1, 2.2, and 2.3 of this appendix. The draft diverter shall be in the normal open condition and the stack shall not be insulated. (Insulation of the stack is no longer required for the vented heater test.) Begin the steady-state performance test by operating the burner and the circulating air blower, on units so equipped, with the adjustments specified by sections 2.4.1 and 2.5 of this appendix, until steady-state conditions are attained as indicated by three successive readings taken 15 minutes apart with a temperature variation of not more than ±3 °F (1.7 C) in the stack gas temperature for vented heaters equipped with draft diverters or ±5 °F (2.8 C) in the flue gas temperature for vented heaters equipped with either draft hoods or direct vent systems. The measurements described in this section are to coincide with the last of these 15 minute readings.
On units employing draft diverters, measure the room temperature (T
On units employing draft hoods or direct vent systems, measure the room temperature (T
Determine the steady-state heat input rate (Qin) including pilot gas by multiplying the measured higher heating value of the test gas by the steady-state gas input rate corrected to standard conditions of 60 °F and 30 inches of mercury. Use measured values of gas temperature and pressure at the meter and the barometric pressure to correct the metered gas flow rate to standard conditions.
After the above test measurements have been completed on units employing draft diverters, secure a sample of the flue gases at the exit of the heat exchanger(s) and determine the concentration of CO
For heaters with single-stage thermostat control (wall mounted electric thermostats), determine the steady-state efficiency at the maximum fuel input rate as specified in section 2.4 of this appendix.
For gas fueled vented heaters equipped with either two stage control or step-modulating control, determine the steady-state efficiency at the maximum fuel input rate and at the reduced fuel input rate, as specified in section 2.4.1 of this appendix.
For manually controlled gas fueled vented heaters with various input rates, determine the steady-state efficiency at a fuel input rate that is within ±5 percent of 50 percent of the maximum rated fuel input rate as indicated on the nameplate of the unit or in the manufacturer's installation and operation manual shipped with the unit. If the heater is designed to use a control that precludes operation at other than maximum rated fuel input rate (single firing rate) determine the steady state efficiency at the maximum rated fuel input rate only.
3.1.2 Oil-fueled vented home heating equipment (including direct vent systems). Set up and adjust the vented heater as specified in sections 2.1, 2.2, and 2.3.4 of this appendix. Begin the steady-state performance test by operating the burner and the circulating air blower, on units so equipped, with the adjustments specified by sections 2.4.2 and 2.5 of this appendix, until steady-state conditions are attained as indicated by a temperature variation of not more than ±5 °F (2.8 °C) in the flue gas temperature in three successive readings taken 15 minutes apart. The measurements described in this section are to coincide with the last of these 15 minutes readings.
For units equipped with power burners, do not allow smoke in the flue to exceed a No. 1 smoke during the steady-state performance test as measured by the procedure described in ASTM D2156-09 (R2018). Maintain the average draft over the fire and in the breeching during the steady-state performance test at that recommended by the manufacturer ±0.005 inches of water gauge.
Measure the room temperature (T
For manually controlled oil fueled vented heaters, determine the steady-state efficiency at a fuel input rate that is within ±5 percent of 50 percent of the maximum fuel input rate; or, if the design of the heater is such that the fuel input rate cannot be set to ±5 percent of 50 percent of the maximum rated fuel input rate, determine the steady-state efficiency at the minimum rated fuel input rate as measured in section 3.1.2 of this appendix for manually controlled oil fueled vented heaters.
3.1.3 Auxiliary Electric Power Measurement. Allow the auxiliary electrical system of a gas or oil vented heater to operate for at least five minutes before recording the maximum auxiliary electric power measurement from the wattmeter. Record the maximum electric power (P
3.2 Jacket loss measurement. Conduct a jacket loss test for vented floor furnaces. Measure the jacket loss (L
3.3 Measurement of the off-cycle losses for vented heaters equipped with thermal stack dampers. Unless specified otherwise, the thermal stack damper should be at the draft diverter exit collar. Attach a five foot length of bare stack to the outlet of the damper. Install thermocouples as specified in section 2.6.1 of this appendix.
For vented heaters equipped with single-stage thermostats, measure the off-cycle losses at the maximum fuel input rate. For vented heaters equipped with two stage thermostats, measure the off-cycle losses at the maximum fuel input rate and at the reduced fuel input rate. For vented heaters equipped with step-modulating thermostats, measure the off-cycle losses at the reduced fuel input rate.
Allow the vented heater to heat up to a steady-state condition. Feed a tracer gas at a constant metered rate into the stack directly above and within one foot above the stack damper. Record tracer gas flow rate and temperature. Measure the tracer gas concentration in the stack at several locations in a horizontal plane through a cross-section of the stack at a point sufficiently above the stack damper to ensure that the tracer gas is well mixed in the stack.
Continuously measure the tracer gas concentration and temperature during a 10-minute cool-down period. Shut the burner off and immediately begin measuring tracer gas concentration in the stack, stack temperature, room temperature, and barometric pressure. Record these values as the midpoint of each one-minute interval between burner shut-down and ten minutes after burner shut-down. Meter response time and sampling delay time shall be considered in timing these measurements.
3.4 Measurement of the effectiveness of electro-mechanical stack dampers. For vented heaters equipped with electro-mechanical stack dampers, measure the cross sectional area of the stack (A
3.5 Pilot light measurement.
3.5.1 Measure the energy input rate to the pilot light (Q
3.5.2 For manually controlled heaters where the pilot light is designed to be turned off by the user when the heater is not in use, that is, turning the control to the OFF position will shut off the gas supply to the burner(s) and to the pilot light, the measurement of Q
3.6 Optional procedure for determining D
Conduct a cool down test by letting the unit heat up until steady-state conditions are reached, as indicated by temperature variation of not more than 5 °F (2.8 °C) in the flue gas temperature in three successive readings taken 15 minutes apart, and then shutting the unit off with the stack or flue damper controls by-passed or adjusted so that the stack or flue damper remains open during the resulting cool down period. If a draft was maintained on oil fueled units in the flue pipe during the steady-state performance test described in section 3.1 of this appendix, maintain the same draft (within a range of −.001 to + .005 inches of water gauge of the average steady-state draft) during this cool down period.
Measure the flue gas mass flow rate (m
Within one minute after the unit is shut off to start the cool down test for determining D
Between 5 and 6 minutes after the unit is shut off to start the cool down test, measure at the exit of the heat exchanger the average flue gas temperature, T*
The rate of the flue gas mass flow through the vented heater and the factors D
3.6.1 Procedure for determining (D
3.6.2 Test Method to Determine Whether the Use of the Default Draft Factors (D
3.6.2.1 Test Conditions. Wait for two minutes following the termination of the vented heater's on-cycle.
3.6.2.2 Location of Test Apparatus
3.6.2.2.1 After all air currents and drafts in the test chamber have been minimized, position the operable smoke stick/pencil as specified, based on the following equipment configuration: for horizontal combustion air intakes, approximately 4 inches from the vertical plane at the termination of the intake vent and 4 inches below the bottom edge of the combustion air intake, or for vertical combustion air intakes, approximately 4 inches horizontal from vent perimeter at the termination of the intake vent and 4 inches down (parallel to the vertical axis of the vent). In the instance where the boiler combustion air intake is closer than 4 inches to the floor, place the smoke device directly on the floor without impeding the flow of smoke.
3.6.2.2.2 Monitor the presence and the direction of the smoke flow.
3.6.2.3 Duration of Test. Continue monitoring the release of smoke for no less than 30 seconds.
3.6.2.4 Test Results
3.6.2.4.1 During visual assessment, determine whether there is any draw of smoke into the combustion air intake.
3.6.2.4.2 If absolutely no smoke is drawn into the combustion air intake, the vented heater meets the requirements to allow use of the default draft factor of 0.05.
3.6.2.4.3 If there is any smoke drawn into the intake, use of default draft factor of 0.05 is prohibited. Proceed with the methods of testing as prescribed in section 3.6 of this appendix, or select the appropriate default draft factor from Table 1.
3.7 Measurement of electrical standby mode and off mode power.
3.7.1 Standby power measurements. With all electrical auxiliaries of the vented heater not activated, measure the standby power (P
3.7.2 Off mode power measurement. If the unit is equipped with a seasonal off switch or there is an expected difference between off mode power and standby mode power, measure off mode power (P
3.8 Condensing vented heaters—measurement of condensate under steady-state and cyclic conditions. Attach condensate drain lines to the vented heater as specified in the manufacturer's I&O manual provided with the unit. The test unit shall be level prior to all testing. A continuous downward slope of drain lines from the unit shall be maintained. The drain lines must facilitate uninterrupted flow of condensate during the test. The condensate collection container must be glass or polished stainless steel to facilitate removal of interior deposits. The collection container shall have a vent opening to the atmosphere, be dried prior to each use, and be at room ambient temperature. The humidity of the room air shall at no time exceed 80 percent relative humidity. For condensing units not designed for collecting and draining condensate, drain lines must be provided during testing that meet the criteria set forth in this section 3.8. Units employing manual controls and units not tested under the optional tracer gas procedures of sections 3.3 and 3.6 of this appendix shall only conduct the steady-state condensate collection test.
3.8.1 Steady-state condensate collection test. Begin steady-state condensate collection concurrently with or immediately after completion of the steady-state testing of section 3.1 of this appendix. The steady-state condensate collection period shall be 30 minutes. Condensate mass shall be measured immediately at the end of the collection period to minimize evaporation loss from the sample. Record fuel input during the 30-minute condensate collection steady-state test period. Measure and record fuel higher heating value (HHV), temperature, and pressures necessary for determining fuel energy input (Q
For units with step-modulating or two stage controls, the steady-state condensate collection test shall be conducted at both the maximum and reduced input rates.
3.8.2 Cyclic condensate collection tests. If existing controls do not allow for cyclical operation of the tested unit, install control devices to allow cyclical operation of the vented heater. Run three consecutive test cycles. For each cycle, operate the unit until flue gas temperatures at the end of each on-cycle, rounded to the nearest whole number, are within 5 °F of each other for two consecutive cycles. On-cycle and off-cycle times are 4 minutes and 13 minutes respectively. Control of ON and OFF operation actions shall be within ±6 seconds of the scheduled time. For fan-type vented heaters, maintain circulating air adjustments as specified in section 2.5 of this appendix. Begin condensate collection at one minute before the on-cycle period of the first test cycle. Remove the container one minute before the end of each off-cycle period. Measure condensate mass for each test-cycle. The error associated with the mass measurement instruments shall not exceed ±0.5 percent of the quantity measured.
Record fuel input during the entire test period starting at the beginning of the on-time period of the first cycle to the beginning of the on-time period of the second cycle, from the beginning of the on-time period of the second cycle to the beginning of the on-time period of the third cycle, etc., for each of the test cycles. Record fuel HHV, temperature, and pressure necessary for determining fuel energy input, Q
For units with step-modulating controls, conduct the cyclic condensate collection test at reduced input rate only. For units with two-stage controls, conduct the cyclic condensate collection test at both maximum and reduced input rates unless the balance-point temperature (T
4.1 Annual fuel utilization efficiency for gas fueled or oil fueled vented home heating equipment equipped without manual controls or with multiple control modes as per 2.11 and without thermal stack dampers. The following procedure determines the annual fuel utilization efficiency for gas fueled or oil fueled vented home heating equipment equipped without manual controls and without thermal stack dampers.
4.1.1 System number. Obtain the system number from Table 1 of this appendix.
4.1.2 Off-cycle flue gas draft factor. Based on the system number, determine the off-cycle flue gas draft factor (D
4.1.3 Off-cycle stack gas draft factor. Based on the system number, determine the off-cycle stack gas draft factor (D
4.1.4 Pilot fraction. Calculate the pilot fraction (P
4.1.5 Jacket loss for floor furnaces. Determine the jacket loss (L
4.1.6 Latent heat loss. For non-condensing vented heaters, obtain the latent heat loss (L
For steady-state conditions:
4.1.6.1 Latent heat gain due to condensation under steady-state conditions. Calculate the latent heat gain (L
4.1.6.2 Heat loss due to hot condensate going down the drain under steady-state conditions. Calculate the steady-state heat loss due to hot condensate going down the drain (L
4.1.6.3 Latent heat gain due to condensation under cyclic conditions. (only for vented heaters tested under the optional tracer gas procedures of section 3.3 or 3.6 of this appendix) Calculate the latent heat gain (L
4.1.6.4 Heat loss due to hot condensate going down the drain under cyclic conditions. (only for vented heaters tested under the optional tracer gas procedures of section 3.3 or 3.6 of this appendix) Calculate the cyclic heat loss due to hot condensate going down the drain (L
4.1.7 Ratio of combustion air mass flow rate to stoichiometric air mass flow rate. Determine the ratio of combustion air mass flow rate to stoichiometric air mass flow rate (R
4.1.8 Ratio of combustion and relief air mass flow rate to stoichiometric air mass flow rate. For vented heaters equipped with either an integral draft diverter or a draft hood, determine the ratio of combustion and relief air mass flow rate to stoichiometric air mass flow rate (R
4.1.9 Sensible heat loss at steady-state operation. For vented heaters equipped with either an integral draft diverter or a draft hood, determine the sensible heat loss at steady-state operation (L
For vented heaters equipped without an integral draft diverter, determine (L
4.1.10 Steady-state efficiency. For vented heaters equipped with single-stage thermostats, calculate the steady-state efficiency (excluding jacket loss), η
For vented heaters equipped with either two stage controls or with step-modulating controls, calculate the steady-state efficiency at the reduced fuel input rate, η
For vented heaters equipped with two stage controls, calculate the steady-state efficiency at the maximum fuel input rate, η
For vented heaters equipped with step-modulating thermostats, calculate the weighted-average steady-state efficiency in the modulating mode, η
4.1.11 Reduced heat output rate. For vented heaters equipped with either two stage thermostats or step-modulating thermostats, calculate the reduced heat output rate
(Q4.1.12 Maximum heat output rate. For vented heaters equipped with either two stage thermostats or step-modulating thermostats, calculate the maximum heat output rate (Q
4.1.13 Ratio of reduced to maximum heat output rates. For vented heaters equipped with either two stage thermostats or step-modulating thermostats, calculate the ratio of reduced to maximum heat output rates (R) expressed as a decimal and defined as:
R = Q4.1.14 Fraction of heating load at reduced operating mode. For vented heaters equipped with either two stage thermostats or step-modulating thermostats, determine the fraction of heating load at the reduced operating mode (X
4.1.15 Fraction of heating load at maximum operating mode or noncycling mode. For vented heaters equipped with either two stage thermostats or step-modulating thermostats, determine the fraction of heating load at the maximum operating mode or noncycling mode (X
4.1.16 Weighted-average steady-state efficiency. For vented heaters equipped with single-stage thermostats, the weighted-average steady-state efficiency (η
For vented heaters equipped with step-modulating controls, η
4.1.17 Annual fuel utilization efficiency. Calculate the annual fuel utilization efficiency (AFUE) expressed as percent and defined as:
4.2 Annual fuel utilization efficiency for gas or oil fueled vented home heating equipment equipped with manual controls. The following procedure determines the annual fuel utilization efficiency for gas or oil fueled vented home heating equipment equipped with manual controls.
4.2.1 Average ratio of stack gas mass flow rate to flue gas mass flow rate at steady-state operation. For vented heaters equipped with either direct vents or direct exhaust or that are outdoor units, the average ratio of stack gas mass flow rate to flue gas mass flow rate at steady-state operation (S/F) shall be equal to unity. (S/F = 1) For all other types of vented heaters, calculate (S/F) defined as:
where:4.2.2 Multiplication factor for infiltration loss during burner on-cycle. Calculate the multiplication factor for infiltration loss during burner on-cycle (K
4.2.3 On-cycle infiltration heat loss. Calculate the on-cycle infiltration heat loss (L
4.2.4 Weighted-average steady-state efficiency.
4.2.4.1 For manually controlled heaters with various input rates the weighted average steady-state efficiency (η
(1) at 50 percent of the maximum fuel input rate as measured in either section 3.1.1 of this appendix for manually controlled gas vented heaters or section 3.1.2 of this appendix for manually controlled oil vented heaters, or
(2) at the minimum fuel input rate as measured in either section 3.1.1 of this appendix for manually controlled gas vented heaters or section 3.1.2 of this appendix for manually controlled oil vented heaters if the design of the heater is such that the ±5 percent of 50 percent of the maximum fuel input rate cannot be set, provided this minimum rate is no greater than 2/3 of the maximum input rate of the heater.
4.2.4.2 For manually controlled heater with one single firing rate the weighted average steady-state efficiency is the steady-state efficiency measured at the single firing rate.
4.2.5 Part-load fuel utilization efficiency. Calculate the part-load fuel utilization efficiency (η
4.2.6 Annual Fuel Utilization Efficiency.
4.2.6.1 For manually controlled vented heaters, calculate the AFUE expressed as a percent and defined as:
where:4.2.6.2 For manually controlled vented heaters where the pilot light can be turned off by the user when the heater is not in use as described in section 3.5.2, calculate the AFUE expressed as a percent and defined as:
4.3 Annual fuel utilization efficiency by the tracer gas method. The annual fuel utilization efficiency shall be determined by the following tracer gas method for all vented heaters equipped with thermal stack dampers.
4.3.1 On-cycle sensible heat loss. For vented heaters equipped with single-stage thermostats, calculate the on-cycle sensible heat loss (L
For vented heaters with step-modulating controls, calculate L
4.3.2 On-cycle infiltration heat loss. For vented heaters equipped with single-stage thermostats, calculate the on-cycle infiltration heat loss (L
For vented heaters equipped with two stage thermostats, calculate L
For vented heaters equipped with step-modulating thermostats, calculate L
4.3.3 Off-cycle sensible heat loss. For vented heaters equipped with single-stage thermostats, calculate the off-cycle sensible heat loss (L
For vented heaters equipped with two stage controls, calculate L
Calculate the off-cycle sensible heat loss (L
4.3.4 Average outdoor temperature. For vented heaters equipped with single-stage thermostats, the average outdoor temperature (T
4.3.5 Off-cycle infiltration heat loss. For vented heaters equipped with single stage thermostats, calculate the off-cycle infiltration heat loss (L
For vented heaters equipped with two stage thermostats, calculate L
Calculate the off-cycle infiltration heat loss (L
4.3.6 Part-load fuel utilization efficiency. Calculate the part-load fuel utilization efficiency (η
4.3.7 Annual Fuel Utilization Efficiency.
Calculate the AFUE expressed as a percent and defined as:
where:4.4 Stack damper effectiveness for vented heaters equipped with electro-mechanical stack dampers. Determine the stack damper effectiveness for vented heaters equipped with electro-mechanical stack dampers (D
4.5 Addition requirements for vented home heating equipment using indoor air for combustion and draft control. For vented home heating equipment using indoor air for combustion and draft control, D
4.5.1 Optional procedure for determining D
For vented heaters in which no draft is maintained during the steady-state or cool down tests, M
For oil fueled vented heaters in which an imposed draft is maintained, as described in section 3.6 of this appendix, M
4.5.2 Optional procedure for determining off-cycle draft factor for flue gas flow for vented heaters. For systems numbered 1 through 10, calculate the off-cycle draft factor for flue gas flow (D
4.5.3 Optional procedure for determining off-cycle draft factor for stack gas flow for vented heaters. Calculate the off-cycle draft factor for stack gas flow (D
4.6 Annual energy consumption.
4.6.1 National average number of burner operating hours. For vented heaters equipped with single stage controls or manual controls, the national average number of burner operating hours (BOH) is defined as:
4.6.1.1 For vented heaters equipped with two stage or step modulating controls the national average number of burner operating hours at the reduced operating mode is defined as:
4.6.1.2 For vented heaters equipped with two stage or step modulating controls the national average number of burner operating hours at the maximum operating mode (BOH
4.6.2 Average annual fuel energy for gas or oil fueled vented heaters. For vented heaters equipped with single stage controls or manual controls, the average annual fuel energy consumption (E
4.6.2.1 For vented heaters equipped with either two stage or step modulating controls E
4.6.3 Average annual auxiliary electrical energy consumption for vented heaters. For vented heaters with single-stage controls or manual controls, the average annual auxiliary electrical consumption (E
4.6.3.1 For vented heaters with two-stage or modulating controls, E
4.6.4 Average annual energy consumption for vented heaters located in a different geographic region of the United States and in buildings with different design heating requirements.
4.6.4.1 Average annual fuel energy consumption for gas or oil fueled vented home heaters located in a different geographic region of the United States and in buildings with different design heating requirements. For gas or oil fueled vented heaters the average annual fuel energy consumption for a specific geographic region and a specific typical design heating requirement (E
4.6.4.2 Average annual auxiliary electrical energy consumption for gas or oil fueled vented home heaters located in a different geographic region of the United States and in buildings with different design heating requirements. For gas or oil fueled vented home heaters the average annual auxiliary electrical energy consumption for a specific geographic region and a specific typical design heating requirement (E
Table 1—Off-Cycle Draft Factors for Flue Gas Flow (D
System number | (D | (D | Burner type | Venting system type 1 | 1 | 1.0 | 1.0 | Atmospheric | Draft hood or diverter. | 2 | 0.4 | 1.0 | Power | Draft hood or diverter. | 3 | 1.0 | 1.0 | Atmospheric | Barometric draft regulator. | 4 | 0.4 | 0.85 | Power | Barometric draft regulator. | 5 | 1.0 | D | Atmospheric | Draft hood or diverter with damper. | 6 | 0.4 | D | Power | Draft hood or diverter with damper. | 7 | 1.0 | D | Atmospheric | Barometric draft regulator with damper. | 8 | 0.4 | D | Power | Barometric draft regulator with damper. | 9 | 1.0 | 0 | Atmospheric | Direct vent. | 10 | 0.4 | 0 | Power | Direct vent. | 11 | D | 0 | Atmospheric | Direct vent with damper. | 12 | 0.4 D | 0 | Power | Direct vent with damper. |
---|
1 Venting systems listed with dampers means electromechanical dampers only.
Table 2—Values of Higher Heating Value (HHV(
Fuels | HHV | A/F | L | A | B | C | D | No. 1 oil | 19,800 | 14.56 | 6.55 | 0.0679 | 14.22 | 0.0179 | 0.167 | No. 2 oil | 19,500 | 14.49 | 6.50 | 0.0667 | 14.34 | 0.0181 | 0.167 | Natural gas | 20,120 | 14.45 | 9.55 | 0.0919 | 10.96 | 0.0175 | 0.171 | Manufactured gas | 18,500 | 11.81 | 10.14 | 0.0965 | 10.10 | 0.0155 | 0.235 | Propane | 21,500 | 15.58 | 7.99 | 0.0841 | 12.60 | 0.0177 | 0.151 | Butane | 20,000 | 15.36 | 7.79 | 0.0808 | 12.93 | 0.0180 | 0.143 |
---|
Table 3—Fraction of Heating Load at Reduced Operating Mode (X1) and at Maximum Operating Mode (X2), Average Outdoor Temperatures (TOA and TOA*), and Balance Point Temperature (TC) for Vented Heaters Equipped With Either Two-Stage Thermostats or Step-Modulating Thermostats
Heat output ratio a | X1 | X2 | TOA | TOA* | TC | 0.20 to 0.24 | .12 | .88 | 57 | 40 | 53 | 0.25 to 0.29 | .16 | .84 | 56 | 39 | 51 | 0.30 to 0.34 | .20 | .80 | 54 | 38 | 49 | 0.35 to 0.39 | .30 | .70 | 53 | 36 | 46 | 0.40 to 0.44 | .36 | .64 | 52 | 35 | 44 | 0.45 to 0.49 | .43 | .57 | 51 | 34 | 42 | 0.50 to 0.54 | .52 | .48 | 50 | 32 | 39 | 0.55 to 0.59 | .60 | .40 | 49 | 30 | 37 | 0.60 to 0.64 | .70 | .30 | 48 | 29 | 34 | 0.65 to 0.69 | .76 | .24 | 47 | 27 | 32 | 0.70 to 0.74 | .84 | .16 | 46 | 25 | 29 | 0.75 to 0.79 | .88 | .12 | 46 | 22 | 27 | 0.80 to 0.84 | .94 | .06 | 45 | 20 | 23 | 0.85 to 0.89 | .96 | .04 | 45 | 18 | 21 | 0.90 to 0.94 | .98 | .02 | 44 | 16 | 19 | 0.95 to 0.99 | .99 | .01 | 44 | 13 | 17 |
---|
a The heat output ratio means the ratio of minimum to maximum heat output rates as defined in 4.1.13.
Table 4—Average Design Heating Requirements for Vented Heaters With Different Output Capacities
Vented heaters output capacity Q | Average design heating requirements (kBtu/hr) | 5,000-7,499 | 5.0 | 7,500-10,499 | 7.5 | 10,500-13,499 | 10.0 | 13,500-16,499 | 12.5 | 16,500-19,499 | 15.0 | 19,500-22,499 | 17.5 | 22,500-26,499 | 20.5 | 26,500-30,499 | 23.5 | 30,500-34,499 | 26.5 | 34,500-38,499 | 30.0 | 38,500-42,499 | 33.5 | 42,500-46,499 | 36.5 | 46,500-51,499 | 40.0 | 51,500-56,499 | 44.0 | 56,500-61,499 | 48.0 | 61,500-66,499 | 52.0 | 66,500-71,499 | 56.0 | 71,500-76,500 | 60.0 |
---|
4.7 Average annual electric standby mode and off mode energy consumption.
Calculate the annual electric standby mode and off mode energy consumption, E