Collapse to view only § 95.50-80 - Location and number of fire extinguishers required for vessels constructed prior to August 22, 2016.

§ 95.50-1 - Application.

(a) The provisions of this subpart, with the exception of §§ 95.50-80 and 95.50-90, as applicable, apply to all vessels, other than unmanned barges and fishing vessels, contracted for on or after November 19, 1952.

(b) Vessels contracted for prior to August 22, 2016 and on or after November 19, 1952, must meet the requirements of § 95.50-80.

(c) Vessels contracted for prior to November 19, 1952, must meet the requirements of § 95.50-90.

[USCG-2012-0196, 81 FR 48264, July 22, 2016]

§ 95.50-5 - [Reserved]

§ 95.50-10 - Location.

(a) Approved portable fire extinguishers and semi-portable fire extinguishing systems must be installed in accordance with table 1 to § 95.50-10(b). The location of the equipment must be to the satisfaction of the Officer in Charge, Marine Inspection. Nothing in this paragraph should be construed as limiting the Officer in Charge, Marine Inspection, from requiring such additional equipment as he or she deems necessary for the proper protection of the vessel.

(b) Table 1 to § 95.50-10(b) indicates the minimum required number and type of extinguisher for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.

Table 95.50-10(b)—Portable Fire Extinguisher and Semi-Portable Fire Extinguishing Systems

Space Minimum required rating Quantity and location Safety Areas 1Wheelhouse or fire control roomNone required. Stairway and elevator enclosuresNone required. Communicating corridors.2-A1 in each main corridor not more than 150 ft apart. (May be located in stairways.) Lifeboat embarkation and lowering stationsNone. Radio room20-B:C 22 required in the vicinity of the exit. 2Accommodations 1Staterooms, toilet spaces, public spaces, offices, lockers, isolated storerooms, pantries, open decks, etcNone required. Service Spaces 1Galleys40-B:C1 for each 2,500 sq ft or fraction thereof suitable for hazards involved. Paint and lamp rooms40-B1 outside space in the vicinity of the exit. Accessible baggage, mail, specie rooms, and storerooms2-A1 for each 2,500 sq ft or fraction thereof located in the vicinity of the exits, either inside or outside the spaces. Carpenter shop and similar spaces2-A1 outside the space in the vicinity of the exit. Machinery SpacesCoal-fired boilers: Bunker and boiler spaceNone required. Oil-fired boilers: Spaces containing oil-fired boilers, either main or auxiliary, or their fuel-oil units40-B
160-B
2 required. 3
1 required. 4
Internal combustion or gas turbine propelling machinery spaces40-B1 for each 1,000 brake horsepower; not less than 2 but not more than 6. 5120-B1 required. 6 7Electric propulsive motors or generators of an open type40-B:C1 for each propulsion motor or generator unit. Enclosed ventilating systems for motors and generators of electric propelling machineryNone required. Auxiliary SpacesInternal combustion or gas turbine40-B1 outside the space in the vicinity of the exit. 7Electric emergency motors or generators40-B:C1 outside the space in the vicinity of the exit. 8SteamNone required. Trunks to machinery spacesNone required. Fuel tanksNone required. Cargo SpacesInaccessible during voyage, including trunks and cargo tanksNone required. Accessible during voyageNone required. Spare Units2-A10 percent of the total number required rounded up. 40-B:C10 percent of the total number required rounded up. 20-B:C1

1 For motorboats, the total number of portable fire extinguishers required for safety areas, accommodation spaces, and service spaces must be one 20-B for motorboats of less than 50 GT and two 20-B ratings for motorboats of 50 GT or more.

2 For vessels on an international voyage, substitute one 20-C in the vicinity of the exit.

3 Vessels of less than 1,000 gross tons require one.

4 Vessels of less than 1,000 gross tons may substitute one 120-B.

5 Only one is required for motorboats.

6 If an oil-burning donkey boiler fitted in space, the 160-B previously required for the protection of the boiler may be substituted. Not required where a fixed carbon dioxide system is installed.

7 Not required on vessels of less than 300 gross tons if the fuel has a flashpoint higher than 110 °F.

8 Not required on vessels of less than 300 gross tons.

(c) Semi-portable fire extinguishing systems must be located in the open so as to be readily seen.

(d) If portable fire extinguishers are not located in the open or behind glass so that they may be readily seen, they may be placed in enclosures together with the firehose, provided such enclosures are marked as required by § 97.37-15 of this subchapter.

(e) Portable fire extinguishers and their stations must be numbered in accordance with § 97.37-23 of this subchapter.

(f) Portable or semi-portable extinguishers, which are required on their nameplates to be protected from freezing, must not be located where freezing temperatures may be expected.

[USCG-2012-0196, 81 FR 48264, July 22, 2016, as amended by USCG-2020-0519, 89 FR 76699, Sept. 18, 2024]

§ 95.50-20 - Semi-portable fire extinguishers.

(a) The frame or support of each semi-portable fire extinguisher required by Table 95.50-10(a) must be welded or otherwise permanently attached to a bulkhead or deck.

(b) If an approved semi-portable fire extinguisher has wheels and is not required by Table 95.50-10(a), it must be securely stowed when not in use to prevent it from rolling out of control under heavy sea conditions.

(c) Semi-portable extinguishers must be fitted with suitable hoses and nozzles, or other practicable means, so that all areas of the space can be protected.

[CGD 77-039, 44 FR 34133, June 14, 1979, as amended by USCG-2012-0196, 81 FR 48265, July 22, 2016]

§ 95.50-80 - Location and number of fire extinguishers required for vessels constructed prior to August 22, 2016.

(a) Vessels contracted for prior to August 22, 2016 must meet the following requirements:

(1) Previously installed extinguishers with extinguishing capacities smaller than what is required in table 95.50-10(a) of this subpart need not be replaced and may be continued in service so long as they are maintained in good condition to the satisfaction of the Officer in Charge, Marine Inspection.

(2) All new equipment and installations must meet the applicable requirements in this subpart for new vessels.

(b) [Reserved]

[USCG-2012-0196, 81 FR 48265, July 22, 2016]

§ 95.50-90 - Vessels contracted for prior to November 19, 1952.

(a) Vessels contracted for prior to November 19, 1952, shall meet the following requirements:

(1) The provisions of §§ 95.50-5 through 95.50-15 shall be met with the exception that existing installations in safety areas and service spaces may be maintained if in the opinion of the Officer in Charge, Marine Inspection, they are in general agreement with the degree of safety prescribed by Table 95.50-10(a). In such cases, minor modifications may be made to the same standard as the original installation: Provided, That in no case will a greater departure from the standards of Table 95.50-10(a) be permitted than presently exists.