Collapse to view only § 95.16-10 - Piping, fittings, valves, nozzles.
- § 95.16-1 - Application.
- § 95.16-5 - Controls.
- § 95.16-10 - Piping, fittings, valves, nozzles.
- § 95.16-15 - Extinguishing agent: Quantity.
- § 95.16-20 - Extinguishing agent: Cylinder storage.
- § 95.16-25 - Manifold and cylinder arrangements.
- § 95.16-30 - Enclosure openings.
- § 95.16-35 - Pressure relief.
- § 95.16-40 - Locked spaces.
- § 95.16-45 - Pre-discharge alarms and time delay devices.
- § 95.16-50 - Instructions.
- § 95.16-60 - System piping installation testing.
- § 95.16-90 - Installations contracted for prior to July 9, 2012.
§ 95.16-1 - Application.
(a) “Clean agent” means a halocarbon or inert gas used as a fire extinguishing agent.
(b) A clean agent extinguishing system must comply with this part. Systems contracted for prior to July 9, 2012, may, as an alternative, comply with 46 CFR 95.16-90.
(c) Each clean agent system must:
(1) Be of a total flooding type to protect against Class B and Class C hazards as defined in 46 CFR 95.50-5;
(2) Address and minimize any hazard to personnel created by the effects of extinguishing agent decomposition products and combustion products, especially the effects of decomposition product hydrogen fluoride (HF), if applicable;
(3) Be accompanied by an approved manufacturer's design, installation, operation, and maintenance manual;
(4) Be used only to protect enclosed spaces;
(5) Not employ electric power for system actuation or controls; and
(6) Not use any source of power for alarms in protected spaces, other than the extinguishing agent, gas from pilot cylinders, or gas from cylinders specifically provided to power the alarms.
§ 95.16-5 - Controls.
(a) At least one releasing station must be installed near the main entrance/exit to the protected space.
(b) System controls must be of an approved type and be suitably protected from damage and located outside the protected space.
(c) Systems must have releasing stations consisting of one control to operate the stop valve to the protected space and a second control to release at least the required amount of agent. These two controls must be located in a box or other enclosure clearly identified for the particular space.
(d) Systems protecting a single space not exceeding 6,000 cubic feet in gross volume may be installed without a stop valve if a suitable horizontal means of escape from the space exists.
(e) Controls may not be located in any space that could be cut off from the operator in the event of fire in the protected space.
(f) Where the extinguishing agent can be released by remote control, the system must have a manual local control at the cylinders.
(g) Systems with remotely operated releasing controls must have mechanical override features.
(h) Automatic discharge arrangements may be used for spaces having a gross volume less than 6,000 cubic feet. However, automatic discharge is required for spaces having a gross volume less than 6,000 cubic feet where the agent is stored in the protected space, as allowed by 46 CFR 95.16-20.
(i) A system designed to use gas pressure from one or more agent storage cylinders and provide pilot pressure to actuate the release of extinguishing agent from other storage cylinders that contain three or more total storage cylinders must be equipped with at least two designated pilot cylinders, each of which is capable of manual control at the pilot cylinder.
§ 95.16-10 - Piping, fittings, valves, nozzles.
(a) Piping, fittings, and valves must be:
(1) In accordance with the manufacturer's approved design, installation, operation, and maintenance manual;
(2) Securely supported and when necessary protected against damage;
(3) Protected inside and out against corrosion; and
(4) Equipped with:
(i) Dead end lines (dirt traps) that extend at least 2 inches beyond the last nozzle of each distribution line and that are closed with a cap or plug; and
(ii) Drains and dirt traps, fitted where necessary to prevent dirt or moisture accumulation and located in accessible locations where possible.
(b) Piping requirements. Piping must be:
(1) Used exclusively for extinguishing system purposes;
(2) Protected by a pressure relief valve in sections where gas pressure can be trapped between closed valves; and
(3) Welded if it passes through living quarters.
(c) Piping prohibitions. Piping must not:
(1) Use rolled groove or cut groove ends; or
(2) Be fitted with drains or other openings if it passes through living quarters.
(d) Valve requirements. Valves for system operation must be:
(1) Outside the protected space, and
(2) Marked, if serving a branch line, to indicate the space the branch line serves.
(e) Valve prohibitions. Valves may not be located in any space that could be cut off from the operator in the event of fire in the protected space.
§ 95.16-15 - Extinguishing agent: Quantity.
A separate supply need not be provided for each space protected, but the total available supply must be at least sufficient for the space requiring the greatest amount.
§ 95.16-20 - Extinguishing agent: Cylinder storage.
(a) Unless installed as required in paragraph (b) of this section, the agent must be stored outside of the protected space. Common bulkheads and decks located between the cylinder storage room and the protected spaces must meet the insulation criteria for Class A-60, as defined in 46 CFR 72.05-10.
(b) The cylinders may be stored inside the protected space, if:
(1) The space does not exceed 6,000 cubic feet gross volume; and
(2) The system can be automatically operated by a pneumatic heat actuator as well as a remote manual control.
(c) The cylinder storage space must be properly ventilated and designed to preclude an anticipated ambient temperature in excess of 130 °Fahrenheit.
(d) The cylinders must be securely fastened and supported as directed in the manufacturer's approved design, installation, operation, and maintenance manual, and where necessary protected against damage.
(e) The cylinders must be mounted so they are readily accessible and capable of easy removal for recharging and inspection and for weighing in the case of halocarbon system cylinders.
(f) The cylinders must be installed to provide a space of at least 2 inches between the deck and the bottom of the cylinders. A tray or other bottom support located 2 inches above the deck is an acceptable arrangement.
(g) The cylinders must be mounted upright, unless otherwise specified in the instruction manual.
(h) All cylinder storage room doors must open outward.
§ 95.16-25 - Manifold and cylinder arrangements.
(a) A check valve must be provided between each cylinder and manifold or distribution piping. The valve must be permanently marked to indicate the direction of flow.
(b) If the same cylinder is used to protect more than one space, normally, closed stop valves must be provided to direct the agent into each protected space.
(c) Each cylinder must be fabricated, tested, and marked in accordance with 46 CFR 147.60(b) and 49 CFR part 180.
(d) The cylinders in a common manifold must be:
(1) Of the same size;
(2) Filled with the same amount of agent; and
(3) Pressurized to the same working pressure.
§ 95.16-30 - Enclosure openings.
(a) If mechanical ventilation is provided for in a protected space, the ventilation system must automatically shut down prior to discharge of the system to that space.
(b) If natural ventilation is provided for in a space protected by a clean agent extinguishing system, the ventilation must be capable of being easily and effectively closed off.
(c) All other openings to a protected space must be capable of being closed. Doors, shutters, or dampers must be installed for openings in the lower portion of the space. Openings in the upper portion of the space must be capable of being closed off either by permanently installed means or by the use of canvas or other material normally carried on the vessel.
§ 95.16-35 - Pressure relief.
Tight compartments, like refrigeration spaces and paint lockers, must have a way to relieve the accumulation of excessive pressure within the compartment when the extinguishing agent is injected.
§ 95.16-40 - Locked spaces.
If a space or enclosure containing extinguishing agent supply or controls is lockable, a key to the space or enclosure must be in a break glass type box conspicuously located adjacent to the opening.
§ 95.16-45 - Pre-discharge alarms and time delay devices.
(a) Each system protecting a space with greater than 6,000 cubic feet gross volume or a space less than 6,000 cubic feet gross volume without a suitable horizontal escape route must have a pneumatic pre-discharge alarm and time delay.
(1) The time delay period must:
(i) Last at least 20 seconds;
(ii) Be approved by the Officer in Charge, Marine Inspection during system installation; and
(iii) Provide enough time for one person to walk from the farthest area of the protected space to the primary exit.
(2) The time delay device must be pneumatically operated and have an accuracy of −0/+20 percent of the rated time delay period throughout the operating temperature range and range of delay settings.
(b) The pre-discharge alarm must:
(1) Sound for the duration of the time delay;
(2) Be conspicuously and centrally located in the protected space and marked as required by 46 CFR 97.37-9;
(3) Depend on the extinguishing agent, gas from a pilot cylinder, or a nitrogen cylinder specifically provided to power the alarm for its source of power; and
(4) Be audible over running machinery.
§ 95.16-50 - Instructions.
(a) Simple, complete operating instructions must be conspicuously located at or near any release station and in the extinguishing agent cylinder storage room.
(b) On a system in which extinguishing agent cylinders are stored outside the protected space, operating instructions must also:
(1) Include a schematic diagram of the system; and
(2) Describe alternate methods of discharging the extinguishing agent into protected spaces should the manual releases or stop valve controls fail to operate.
§ 95.16-60 - System piping installation testing.
(a) Halocarbon systems. A pressure test using the extinguishing agent, air or inert gas, must be conducted on halocarbon system discharge piping on completion of piping installation and before extinguishing agent cylinders are connected.
(1) Except as otherwise specified in this section:
(i) Piping from the cylinders to the stop valves or selector valves must be subjected to a pressure of 1 1/2 times the cylinder charging pressure at 70 °Fahrenheit; and
(ii) The leakage during a 2-minute period must not exceed a pressure drop of 10 percent of the test pressure.
(2) Individual branch lines to a protected space must be tested as described in paragraph (a)(1) of this section, except that:
(i) The pressure must be 150 pounds per square inch; and
(ii) Distribution piping must be capped within the protected space at the first joint upstream of the nozzles.
(3) Pneumatic actuation piping must be tested as described in paragraph (a)(1) of this section.
(b) Inert gas systems. A pressure test using air or inert gas must be conducted on each inert gas system's piping on completion of piping installation and before extinguishing agent cylinders are connected.
(1) Except as otherwise specified in this section:
(i) Piping from the cylinders to the stop valves or selector valves must be subjected to a pressure of 1,000 pounds per square inch (psi) at 70 °Fahrenheit; and
(ii) The leakage during a 2-minute period must not exceed a pressure drop of 100 psi.
(2) Individual branch lines to a protected space must be tested as described in paragraph (b)(1) of this section, except that:
(i) The pressure must be 600 psi; and
(ii) Distribution piping must be capped within the protected space at the first joint upstream of the nozzles.
(3) Pneumatic actuation piping must be tested as described in paragraph (b)(1) of this section.
(c) Small independent systems. In lieu of test requirements in paragraphs (a) or (b) of this section, a small independent halocarbon or inert gas system, like those found in emergency generator rooms and paint lockers, may be tested by blowing out the piping with air pressure of at least 100 psi, if:
(1) There are no valves in the system discharge piping; and
(2) There is not more than one change in direction between the agent container and the discharge nozzle.
§ 95.16-90 - Installations contracted for prior to July 9, 2012.
Installations contracted for prior to July 9, 2012, must meet the requirements of this subpart unless previously approved existing arrangements, materials, and facilities are:
(a) Maintained in good condition to the satisfaction of the Officer in Charge, Marine Inspection; and
(b) Subjected to no more than minor repairs or alterations implemented to the same standards as the original installation.