Collapse to view only § 113.10-7 - Connection boxes.
- § 113.10-1 - Approved equipment.
- § 113.10-3 - Cable runs.
- § 113.10-5 - Common return.
- § 113.10-7 - Connection boxes.
- § 113.10-9 - Power supply.
§ 113.10-1 - Approved equipment.
Each alarm annunciator, fire detector, test station, manual station, and vibrating bell must be approved under Subpart 161.002 of this chapter and meet the requirements of this subpart.
§ 113.10-3 - Cable runs.
Cable runs between the fire alarm annunciator and fire detecting or fire alarm zones must be as direct as practicable and, where practicable, must not be in staterooms, lockers, or other enclosed spaces in order to reduce the risk of damage by a localized fire or other cause.
§ 113.10-5 - Common return.
A conductor must not be used as a common return from more than one zone.
§ 113.10-7 - Connection boxes.
Each connection box must be constructed in accordance with Type 4 or 4X of NEMA 250 or IP 56 of IEC 60529:2013 (both incorporated by reference; see 46 CFR 110.10-1) requirements.
§ 113.10-9 - Power supply.
(a) General. There must be at least two sources of power for the electrical equipment of each fire detecting and alarm system. The normal source must be the main power source. The other source must be the emergency power source or an automatically charged battery. If the other source is an automatically charged battery, the charger must be supplied from the final emergency power source. Upon loss of power to the system from the normal source, the system must be automatically supplied from the other source.
(b) Batteries. Each battery used in a fire detecting and alarm system must meet Subpart 111.15 of this chapter.
(c) Capacity of power supply branch circuit. The capacity of each branch circuit providing power to a fire detection or alarm system must not be less than 125 percent of the maximum load.