§ 111.75-1 - Lighting feeders.
(a) Passenger vessels. On a passenger vessel with fire bulkheads forming main vertical and horizontal fire zones, the lighting distribution system, including low location egress lighting where installed, must be arranged so that, to the maximum extent possible, a fire in any main vertical and horizontal fire zone does not interfere with the lighting in any other fire zone. This requirement is met if main and emergency feeders passing through any zone are separated both vertically and horizontally as widely as practicable.
(b) Machinery spaces. Lighting for enginerooms, boilerrooms, and auxiliary machinery spaces must be supplied from two or more feeders. One of these feeders must be a ship's service feeder.
Note:Special requirements for emergency lighting, feeders, and branch circuits are in subpart 112.43 of this chapter.
§ 111.75-5 - Lighting branch circuits.
(a) Loads. A lighting distribution panel must not supply branch circuits rated at over 30 amperes.
(b) Connected load. The connected loads on a lighting branch circuit must not be more than 80 percent of the rating of the overcurrent protective device, computed on the basis of the fixture ratings and in accordance with Section 9.4.2 of IEEE 45.1-2017 (incorporated by reference; see § 110.10-1 of this subchapter).
(c) Lighting fixtures on lighting circuits. Each lighting fixture must be on a lighting branch circuit.
(d) Overcurrent protection. Each lighting branch circuit must be protected by an overcurrent device rated at 20 amperes or less, except as allowed under paragraph (e) of this section.
(e) 25 or 30 ampere lighting branch circuits. Lighting branch circuits rated at 25 and 30 amperes supplying only fixed nonswitched lighting fixtures for cargo hold or deck lighting having only lampholders of the mogul type, or other lampholding devices required for lamps of more than 300 watts, may be supplied by a 30 ampere branch circuit wired with at least No. 10 AWG (5.3 mm 2) conductors if each fixture wire used in wiring each lighting fixture is No. 12 AWG (3.3 mm 2) or larger.
§ 111.75-15 - Lighting requirements.
(a) Lights in passageways, public spaces, and berthing compartments. The supply to lights in each passageway, public space, or berthing compartment accommodating more than 25 persons must be divided between two or more branch circuits, one of which may be an emergency branch circuit.
(b) Lights in machinery spaces. Alternate groups of lights in an engineroom, boilerroom, or auxiliary machinery space must be arranged so that the failure of one branch circuit does not leave an area without light.
(c) Illumination of passenger and crew spaces. (1) Each space used by passengers or crew must be fitted with lighting that provides for a safe habitable and working environment under normal conditions.
(2) Sufficient illumination must be provided by the emergency lighting source under emergency conditions to effect damage control procedures and to provide for safe egress from each space.
(d) Berth lights. Each crew berth must have a fixed berth light that is not wired with a flexible cord. The berth light must have minimum horizontal projection so that the light may not be covered with bedding.
(e) Exit lights. Each exit light required on passenger vessels under § 112.15-1 of this subchapter must have the word “Exit” in red block letters at least 2 inches (50 mm) high.
(f) Pilot ladders. There must be a means for lighting each station from which a pilot may be deployed.
§ 111.75-16 - Lighting of survival craft and rescue boats.
(a) During preparation, launching, and recovery, each survival craft and rescue boat, its launching appliance, and the area of water into which it is to be launched or recovered must be adequately illuminated by lighting supplied from the emergency power source.
(b) The arrangement of circuits must be such that the lighting for adjacent launching stations for survival craft or rescue boats is supplied by different branch circuits.
§ 111.75-17 - Navigation lights.
Each navigation light system must meet the following:
(a) Feeders. On vessels required to have a final emergency power source by § 112.05-5(a) of this chapter, each navigation light panel must be supplied by a feeder from the emergency switchboard (see § 112.43-13). The feeder must be protected by overcurrent devices rated or set at a value of at least twice that of the navigation light panel main fuses.
(b) Navigation light indicator panel. Each self-propelled vessel must have a navigation light indicator panel in the navigating bridge to control side, masthead, and stern lights. The panel must visually and audibly signal the failure of each of these navigation lights. Each light source must be connected to a separate fused branch circuit. The panel must have a fused feeder disconnect switch, and the fuses must have at least twice the rating of the largest branch circuit fuse and must be greater than the maximum panel load.
(c) Dual light sources. Each self-propelled vessel must have duplicate light sources for the side, masthead, and stern lights.
(d) Navigation lights. Each navigation light must meet the following:
(1) Meet the technical details of the applicable navigation rules.
(2) Be certified by an independent laboratory to the requirements of ANSI/UL 1104 or EN 14744 (incorporated by reference; see § 110.10-1 of this subchapter) or an equivalent standard under § 110.20-1 of this subchapter. Portable battery powered navigation lights need only be certified to the requirements of ANSI/UL 1104 applicable to those lights.
(3) Be labeled with a label stating the following:
(i) “MEETS __________.” (Insert the identification name or number of the standard under paragraph (d)(2) of this section to which the light was type-tested.)
(ii) “TESTED BY __________.” (Insert the name or registered certification mark of the independent laboratory that tested the fixture to the standard under paragraph (d)(2) of this section).
(iii) Manufacturer's name.
(iv) Model number.
(v) Visibility of the light in nautical miles.
(vi) Date on which the fixture was type-tested.
(vii) Identification of bulb used in the compliance test.
(4) If it is a flashing light, have its intensity determined by the formula:
Ie = G/(0.2 + t2−t1) Where Ie = Luminous Intensity. G = Integral of Idt evaluated between the limits of t1 and t2. t1 = Time in seconds of the beginning of the flash. t2 = Time in seconds of the end of the flash. I = Instantaneous intensity during the flash. Note:The limits, t1 and t2, are to be chosen so as to maximize Ie.
§ 111.75-18 - Signaling lights.
Each self-propelled vessel over 150 gross tons when engaged on an international voyage must have on board an approved daylight signaling lamp that meets ISO 25861 (incorporated by reference, see § 110.10-1 of this subchapter).
§ 111.75-20 - Luminaries (lighting fixtures).
(a) The construction of each luminaire (lighting fixture) for a non-hazardous location must meet ANSI/UL 1598A, or IEC 60092-306:2009 (both incorporated by reference; see § 110.10-1 of this subchapter).
(b) Nonemergency and inside-type decorative luminaires in environmentally protected, nonhazardous locations must meet the applicable luminaire-type requirements of ANSI/UL 1598 or IEC 60092-306:2009 (both incorporated by reference; see § 110.10-1 of this subchapter). These luminaires must also meet Clauses 7.4, 8.1, 8.3, 11.2, 13.4, and 17.2 of ANSI/UL 1598A (incorporated by reference; see § 110.10-1 of this subchapter), except in an accommodation space, navigating bridge, gyro room, radio room, galley, or similar space where it is not subject to damage.
(c) Each tablelamp, desklamp, floorlamp, and similar equipment must be secured in place so that it cannot be displaced by the roll or pitch of the vessel.