Collapse to view only § 111.55-3 - Circuit connections.
§ 111.55-1 - General.
(a) Each switch must meet Article 404 of NFPA 70 (incorporated by reference; see Ҥ 110.10-1 of this subchapter).
(b) Each switch that is in the weather must be in a watertight enclosure and be externally operable.
§ 111.55-3 - Circuit connections.
The load side of each circuit must be connected to the fuse end of a fused-switch or to the coil end of a circuit breaker, except a generator which is connected to either end of a circuit breaker.