§ 111.33-1 - General.
This subpart is applicable to all power semiconductor converter systems. In addition to the regulations contained in this subpart, the requirements of §§ 111.30-11 and 111.30-19 of this part must be met, if applicable.
§ 111.33-3 - Nameplate data.
(a) Each semiconductor converter system must have a nameplate of durable material affixed to the unit that meets the requirements of—
(1) Section 4.31.19.12 of IEEE 45.2-2011 (incorporated by reference; see 46 CFR 110.10-1); or
(2) Clause 8 of IEC 60092-304:1980 (incorporated by reference; see 46 CFR 110.10-1).
(b) Each semiconductor rectifier system must have a nameplate containing the words “marine semiconductor rectifier,” and the following information:
(1) Manufacturer's name and address.
(2) Manufacturer's serial number.
(3) Type.
(4) Rated AC volts.
(5) Rated AC amperes.
(6) Number of phases.
(7) Frequency.
(8) Rated DC volts.
(9) Rated DC amperes.
(10) Ambient temperature range.
(11) Duty cycle.
(12) Cooling medium.
(c) If, on small converters, the information required by paragraph (a) of this section cannot be shown because of space limitations, the nameplate must be at least large enough to contain the manufacturer's name and serial number. The remaining information must be shown on the schematic diagram.
§ 111.33-5 - Installation.
Each semiconductor converter system must meet the installation requirements, as appropriate, of—
(a) Sections 4.31.19.2, 4.31.19.7, and 4.31.19.8 of IEEE 45.2-2011 (incorporated by reference; see § 110.10-1 of this subchapter); or
(b) IEC 60092-304:1980 (incorporated by reference; see § 110.10-1 of this subchapter).
§ 111.33-7 - Alarms and shutdowns.
Each power semiconductor converter must have a high temperature alarm or shutdown, except as provided in § 111.33-11.
§ 111.33-9 - Ventilation exhaust.
The exhaust of each forced-air semiconductor converter system must:
(a) Terminate in a location other than a hazardous location under Subpart 111.105 of this part; and
(b) Not impinge upon any other electric device.
§ 111.33-11 - Propulsion systems.
Each power semiconductor converter system in a propulsion system must meet sections 4-8-5/5.17.8 and 4-8-5/5.17.9 of ABS Marine Vessel Rules (incorporated by reference; see § 110.10-1 of this subchapter), except that each one for mobile offshore drilling units must meet the requirements in section 6-1-7/12 of ABS MOU Rules (incorporated by reference; see § 110.10-1 of this subchapter).