Collapse to view only § 111.25-5 - [Reserved]

§ 111.25-1 - General requirements.

The requirements for generators contained in § 111.12-5 apply to motors.

[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 62 FR 23908, May 1, 1997]

§ 111.25-5 - [Reserved]

§ 111.25-15 - Duty cycle.

Each motor must be rated for continuous duty, except a motor for an application listed in Table 111.25-15 or a similar duty must meet the minimum short-time rating stated in the table.

Table 111.25-15

Application of motor Minimum short-time rating of motor, in hours Deck winch and direct acting capstanHalf. Deck winch with hydraulic transmissionContinuous at no load followed by 1/2 hr. at full load. Direct acting windlassOne fourth. Windlass with hydraulic transmissionHalf hour idle pump operation, followed by 1/4 hr. full load operation. Steering gear, direct actingOne. Steering gear, indirect driveContinuous operation at 15 pct. load followed by 1 hr. at full load. Watertight door operators1/12. Boat winches1/12.