Collapse to view only § 77.807-3 - Movement of equipment; minimum distance from high-voltage lines.
- § 77.800 - High-voltage circuits; circuit breakers.
- § 77.800-1 - Testing, examination, and maintenance of circuit breakers; procedures.
- § 77.800-2 - Testing, examination, and maintenance of circuit breakers; record.
- § 77.801 - Grounding resistors.
- § 77.801-1 - Grounding resistors; continuous current rating.
- § 77.802 - Protection of high-voltage circuits; neutral grounding resistors; disconnecting devices.
- § 77.803 - Fail safe ground check circuits on high-voltage resistance grounded systems.
- § 77.803-1 - Fail safe ground check circuits; maximum voltage.
- § 77.803-2 - Ground check systems not employing pilot check wires; approval by the Secretary.
- § 77.804 - High-voltage trailing cables; minimum design requirements.
- § 77.805 - Cable couplers and connection boxes; minimum design requirements.
- § 77.806 - Connection of single-phase loads.
- § 77.807 - Installation of high-voltage transmission cables.
- § 77.807-1 - High-voltage powerlines; clearances above ground.
- § 77.807-2 - Booms and masts; minimum distance from high-voltage lines.
- § 77.807-3 - Movement of equipment; minimum distance from high-voltage lines.
- § 77.808 - Disconnecting devices.
- § 77.809 - Identification of circuit breakers and disconnecting switches.
- § 77.810 - High-voltage equipment; grounding.
- § 77.811 - Movement of portable substations and transformers.
§ 77.800 - High-voltage circuits; circuit breakers.
High-voltage circuits supplying power to portable or mobile equipment shall be protected by suitable circuit breakers of adequate interrupting capacity which are properly tested and maintained and equipped with devices to provide protection against under voltage, grounded phase, short circuit and overcurrent. High-voltage circuits supplying power to stationary equipment shall be protected against overloads by either a circuit breaker or fuses of the correct type and capacity.
§ 77.800-1 - Testing, examination, and maintenance of circuit breakers; procedures.
(a) Circuit breakers and their auxiliary devices protecting high-voltage circuits to portable or mobile equipment shall be tested and examined at least once each month by a person qualified as provided in § 77.103.
(b) Tests shall include:
(1) Breaking continuity of the ground check conductor where ground check monitoring is used; and,
(2) Actuating any of the auxiliary protective relays.
(c) Examination shall include visual observation of all components of the circuit breaker and its auxiliary devices, and such repairs or adjustments as are indicated by such tests and examinations shall be carried out immediately.
§ 77.800-2 - Testing, examination, and maintenance of circuit breakers; record.
The operator shall maintain a written record of each test, examination, repair, or adjustment of all circuit breakers protecting high-voltage circuits. Such record shall be kept in a book approved by the Secretary.
§ 77.801 - Grounding resistors.
The grounding resistor, where required, shall be of the proper ohmic value to limit the voltage drop in the grounding circuit external to the resistor to not more than 100 volts under fault conditions. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system.
§ 77.801-1 - Grounding resistors; continuous current rating.
The ground fault current rating of grounding resistors shall meet the “extended time rating” set forth in American Institute of Electrical Engineers, Standard No. 32.
§ 77.802 - Protection of high-voltage circuits; neutral grounding resistors; disconnecting devices.
High-voltage circuits supplying portable or mobile equipment shall contain either a direct or derived neutral which shall be grounded through a suitable resistor at the source transformers, and a grounding circuit, originating at the grounded side of the grounding resistor, shall extend along with the power conductors and serve as a grounding conductor for the frames of all high-voltage equipment supplied power from that circuit, except that the Secretary or his authorized representative may permit other high-voltage circuits to feed stationary electrical equipment, if he finds that such exception will not pose a hazard to the miners. Disconnecting devices shall be installed and so equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected.
§ 77.803 - Fail safe ground check circuits on high-voltage resistance grounded systems.
On and after September 30, 1971, all high-voltage, resistance grounded systems shall include a fail safe ground check circuit or other no less effective device approved by the Secretary to monitor continuously the grounding circuit to assure continuity. The fail safe ground check circuit shall cause the circuit breaker to open when either the ground or ground check wire is broken.
§ 77.803-1 - Fail safe ground check circuits; maximum voltage.
The maximum voltage used for ground check circuits under § 77.803 shall not exceed 96 volts.
§ 77.803-2 - Ground check systems not employing pilot check wires; approval by the Secretary.
Ground check systems not employing pilot check wires shall be approved by the Secretary only if it is determined that the system includes a fail safe design which will cause the circuit interrupter to open when ground continuity is broken.
§ 77.804 - High-voltage trailing cables; minimum design requirements.
(a) High-voltage trailing cables used in resistance grounded systems shall be equipped with metallic shields around each power conductor with one or more ground conductors having a total cross-sectional area of not less than one-half the power conductor, and with an insulated conductor for the ground continuity check circuit. External ground check conductors may be used if they are not smaller than No. 8 (AWG) and have an insulation rated at least 600 volts.
(b) All such high-voltage trailing cables shall be adequate for the intended current and voltage. Splices made in such cables shall provide continuity of all components.
§ 77.805 - Cable couplers and connection boxes; minimum design requirements.
(a)(1) Couplers that are used in medium- or high-voltage power circuits shall be of the three-phase type and enclosed in a full metallic shell, except that the Secretary may permit, under such guidelines as he may prescribe, no less effective couplers constructed of materials other than metal.
(2) Cable couplers shall be adequate for the intended current and voltage.
(3) Cable couplers with any metal exposed shall be grounded to the ground conductor in the cable.
(4) Couplers shall be constructed to cause the ground check continuity conductor to break first and the ground conductor last when being uncoupled when pilot check circuits are used.
(b) Cable connection boxes shall be of substantial construction and designed to guard all energized parts from personal contact.
§ 77.806 - Connection of single-phase loads.
Single-phase loads, such as transformer primaries, shall be connected phase to phase in resistance grounded systems.
§ 77.807 - Installation of high-voltage transmission cables.
High-voltage transmission cables shall be installed or placed so as to afford protection against damage. They shall be placed to prevent contact with low-voltage or communication circuits.
§ 77.807-1 - High-voltage powerlines; clearances above ground.
High-voltage powerlines located above driveways, haulageways, and railroad tracks shall be installed to provide the minimum vertical clearance specified in National Electrical Safety Code: Provided, however, That in no event shall any high-voltage powerline be installed less than 15 feet above ground.
§ 77.807-2 - Booms and masts; minimum distance from high-voltage lines.
The booms and masts of equipment operated on the surface of any coal mine shall not be operated within 10 feet of an energized overhead powerline. Where the voltage of overhead powerlines is 69,000 volts, or more, the minimum distance from the boom or mast shall be as follows:
Nominal power line voltage (in 1,000 volts) | Minimum distance (feet) | 69 to 114 | 12 | 115 to 229 | 15 | 230 to 344 | 20 | 345 to 499 | 25 | 500 or more | 35 |
---|
§ 77.807-3 - Movement of equipment; minimum distance from high-voltage lines.
When any part of any equipment operated on the surface of any coal mine is required to pass under or by any energized high-voltage powerline and the clearance between such equipment and powerline is less than that specified in § 77.807-2 for booms and masts, such powerlines shall be deenergized or other precautions shall be taken.
§ 77.808 - Disconnecting devices.
Disconnecting devices shall be installed at the beginning of each branch line in high-voltage circuits and they shall be equipped or designed in such a manner that it can be determined by visual observation that the circuit is deenergized when such devices are open.
§ 77.809 - Identification of circuit breakers and disconnecting switches.
Circuit breakers and disconnecting switches shall be labeled to show which units they control, unless identification can be made readily by location.
§ 77.810 - High-voltage equipment; grounding.
Frames, supporting structures, and enclosures of stationary, portable, or mobile high-voltage equipment shall be effectively grounded.
§ 77.811 - Movement of portable substations and transformers.
Portable substations and transformers shall be deenergized before they are moved from one location to another.