Collapse to view only § 75.1323 - Blasting circuits.
- § 75.1300 - Definitions.
- § 75.1301 - Qualified person.
- § 75.1310 - Explosives and blasting equipment.
- § 75.1311 - Transporting explosives and detonators.
- § 75.1312 - Explosives and detonators in underground magazines.
- § 75.1313 - Explosives and detonators outside of magazines.
- § 75.1314 - Sheathed explosive units.
- § 75.1315 - Boreholes for explosives.
- § 75.1316 - Preparation before blasting.
- § 75.1317 - Primer cartridges.
- § 75.1318 - Loading boreholes.
- § 75.1319 - Weight of explosives permitted in boreholes in bituminous and lignite mines.
- § 75.1320 - Multiple-shot blasting.
- § 75.1321 - Permits for firing more than 20 boreholes and for use of nonpermissible blasting units.
- § 75.1322 - Stemming boreholes.
- § 75.1323 - Blasting circuits.
- § 75.1324 - Methane concentration and tests.
- § 75.1325 - Firing procedures.
- § 75.1326 - Examination after blasting.
- § 75.1327 - Misfires.
- § 75.1328 - Damaged or deteriorated explosives and detonators.
§ 75.1300 - Definitions.
The following definitions apply in this subpart.
Approval. A document issued by MSHA which states that an explosive or explosive unit has met the requirements of this part and which authorizes an approval marking identifying the explosive or explosive unit as approved as permissible.
Battery starting. The use of unconfined explosives to start the flow of coal down a breast or chute in an anthracite mine.
Blasting off the solid. Blasting the working face without providing a second free face by cutting, shearing or other method before blasting.
Instantaneous detonator. An electric detonator that fires within 6 milliseconds after application of the firing current.
Laminated partition. A partition composed of the following material and minimum nominal dimensions: 1/2-inch thick plywood, 1/2-inch thick gypsum wall board, 1/8-inch thick low carbon steel and 1/4-inch thick plywood, bonded together in that order.
Opener hole. The first hole or holes fired in a round blasted off the solid to create an additional free face.
Permissible blasting unit. A device that has been approved by MSHA and that is used for firing electric detonators.
Permissible explosive. Any substance, compound or mixture which is approved by MSHA and whose primary purpose is to function by explosion.
Round. A group of boreholes fired or intended to be fired in a continuous sequence with one application of the firing current.
Sheathed explosive unit. A device consisting of an approved or permissible explosive covered by a sheath encased in a sealed covering and designed to be fired outside the confines of a borehole.
Short-delay electric detonator. An electric detonator with a designated delay period of 25 to 1,000 milliseconds.
§ 75.1301 - Qualified person.
(a) A qualified person under this subpart is a person who—
(1) Is certified or qualified to use explosives by the State in which the mine is located provided that the State requires a demonstration of ability to safely use permissible explosives as prescribed by this subpart effective January 17, 1989; or
(2) In States that do not certify or qualify persons to use explosives required by this section, has at least 1 year of experience working in an underground coal mine that includes direct involvement with procedures for handling, loading, and preparing explosives for blasting and demonstrates to an authorized representative of the Secretary the ability to use permissible explosives safely.
(b) Persons qualified or certified by a State to use permissible explosives in underground coal mines as of May 17, 1989, are considered qualified under this section even though their State program did not contain a demonstration of ability requirement.
§ 75.1310 - Explosives and blasting equipment.
(a) Only permissible explosives, approved sheathed explosive units, and permissible blasting units shall be taken or used underground.
(b) Black blasting powder, aluminum-cased detonators, aluminum-alloy-cased detonators, detonators with aluminum leg wires, and safety fuses shall not be taken or used underground.
(c) Explosives shall be fired only with a permissible blasting unit used in a manner consistent with its approval. Blasting units approved by MSHA that have approval labels specifying use with short-delay detonators with delay periods between 25-500 milliseconds are accepted to fire short-delay detonators up to 1,000 milliseconds, instantaneous detonators and long period delay detonators for anthracite mines.
(d) Permissible explosives and sheathed explosive units shall not be used underground when they are below the minimum product firing temperature specified by the approval. Explosives previously approved which do not specify a minimum firing temperature are permissible for use so long as the present approval is maintained.
(e) Electric detonators shall be compatible with the blasting unit and have sufficient strength to initiate the explosives being used.
§ 75.1311 - Transporting explosives and detonators.
(a) When explosives and detonators are to be transported underground—
(1) They shall be enclosed in separate, substantially constructed containers made of nonconductive material, with no metal or other conductive materials exposed inside, except as specified in paragraph (d) of this section; and
(2) Each container of explosives and of detonators shall be indelibly marked with a readily visible warning identifying the contents.
(b) When explosives and detonators are transported by any cars or vehicles—
(1) The cars or vehicles shall be marked with warnings to identify the contents as explosive. The warnings shall be readily visible to miners approaching from any direction and in indelible letters;
(2) Explosives and detonators shall be transported either in separate cars or vehicles, or if in the same cars or vehicles as follows:
(i) Class A and Class C detonators in quantities greater than 1,000 shall be kept in the original containers as shipped from the manufacturer and separated from explosives by a hardwood partition at least 4 inches thick, a laminated partition or equivalent; and
(ii) Class A and Class C detonators in quantities of no more than 1,000 shall be separated from explosives by a hardwood partition at least 4 inches thick, a laminated partition or equivalent.
(3) No persons, other than those necessary to operate the equipment or to accompany the explosives and detonators, shall be transported with explosives and detonators, and
(4) When explosives and detonators are transported using trolley locomotives—
(i) Trips carrying explosives and detonators shall be separated from all other mantrips by at least a 5-minute interval; and
(ii) Cars containing explosives or detonators shall be separated from the locomotives by at least one car that is empty or that contains noncombustible materials.
(c) When explosives and detonators are transported on conveyor belts—
(1) Containers of explosives shall be separated from containers of detonators by at least 50 feet;
(2) At least 6 inches of clearance shall be maintained between the top of any container of explosives or container of detonators and the mine roof or other obstruction;
(3) Except when persons are riding the belt to accompany explosives or detonators, a person shall be at each transfer point between belts and at the unloading location; and
(4) Conveyor belts shall be stopped before explosives or detonators are loaded or unloaded.
(d) When explosives and detonators are transported by hand they shall be carried in separate, nonconductive, closed containers.
§ 75.1312 - Explosives and detonators in underground magazines.
(a) The quantity of explosives kept underground shall not be more than is needed for 48 hours of use.
(b) Except as provided in § 75.1313, explosives and detonators taken underground shall be kept in—
(1) Separate, closed magazines at least 5 feet apart; or
(2) The same closed magazine when—
(i) Separated by a hardwood partition at least 4 inches thick; or
(ii) Separated by a laminated partition; or
(iii) Separated by a device that is equivalent.
(c) Only explosives and detonators shall be kept in underground magazines.
(d) Magazines shall be substantially constructed and all interior surfaces shall be made of nonconductive material, with no metal or other conductive material exposed inside.
(e) All magazines shall be—
(1) Located at least 25 feet from roadways and any source of electric current;
(2) Located out of the direct line of the forces from blasting; and
(3) Kept as dry as practicable.
(f) Magazine locations shall be posted with indelibly marked and readily visible warnings indicating the presence of explosives.
(g) Only materials and equipment to be used in blasting shall be stored at magazine locations.
§ 75.1313 - Explosives and detonators outside of magazines.
(a) The quantity of explosives outside a magazine for use in a working section or other area where blasting is to be performed shall—
(1) Not exceed 100 pounds; or
(2) Not exceed the amount necessary to blast one round when more than 100 pounds of explosives is required.
(b) Explosives and detonators outside a magazine that are not being transported or prepared for loading boreholes shall be kept in closed separate containers made of nonconductive material with no metal or other conductive material exposed inside and the containers shall be—
(1) At least 15 feet from any source of electric current;
(2) Out of the direct line of the forces from blasting;
(3) In a location to prevent damage by mobile equipment; and
(4) Kept as dry as practicable.
(c) Explosives and detonators not used during the shift shall be returned to a magazine by the end of the shift.
§ 75.1314 - Sheathed explosive units.
(a) A separate instantaneous detonator shall be used to fire each sheathed explosive unit.
(b) Sheathed explosive units shall be primed and placed in position for firing only by a qualified person or a person working in the presence of and under the direction of a qualified person. To prime a sheathed explosive unit, the entire detonator shall be inserted into the detonator well of the unit and be held securely in place.
(c) Sheathed explosive units shall not be primed until immediately before the units are placed where they are to be fired. A sheathed explosive unit shall not be primed if it is damaged or deteriorated.
(d) Except in anthracite mines, rock dust shall be applied to the roof, ribs and floor within a 40-foot radius of the location where the sheathed explosive units are to be fired.
(e) No more than three sheathed explosive units shall be fired at one time.
(f) No sheathed explosive unit shall be fired in contact with another sheathed explosive unit.
§ 75.1315 - Boreholes for explosives.
(a) All explosives fired underground shall be confined in boreholes except—
(1) Sheathed explosives units and other explosive units approved by MSHA for firing outside the confines of a borehole; and
(2) Shots fired in anthracite mines for battery starting or for blasting coal overhangs. No person shall go inside a battery to start the flow of material.
(b) Each borehole in coal for explosives shall be at least 24 inches from any other borehole and from any free face, unless prohibited by the thickness of the coal seam.
(c) Each borehole in rock for explosives shall be at least 18 inches from any other borehole in rock, at least 24 inches from any other borehole in coal, and at least 18 inches from any free face.
(d) No borehole that has contained explosives shall be used for starting any other hole.
(e) When blasting slab rounds off the solid, opener holes shall not be drilled beyond the rib line.
(f) When coal is cut for blasting, the coal shall be supported if necessary to maintain the stability of the column of explosives in each borehole.
§ 75.1316 - Preparation before blasting.
(a)(1) All nonbattery-powered electric equipment, including cables, located within 50 feet from boreholes to be loaded with explosives or the sites where sheathed explosive units are to be placed and fired shall be deenergized or removed to at least 50 feet from these locations before priming of explosives. Battery-powered equipment shall be removed to at least 50 feet from these locations before priming of explosives.
(2) As an alternative to paragraph (a)(1) of this section, electric equipment, including cables, need not be deenergized or removed if located at least 25 feet from these locations provided stray current tests conducted prior to priming the explosives detect stray currents of 0.05 ampere or less through a 1-ohm resistor.
(i) Tests shall be made at floor locations on the perimeter, on energized equipment frames and on repaired areas of energized cables within the area between 25 to 50 feet from the locations where the explosives are to be primed.
(ii) Tests shall be conducted using a blasting multimeter or other instrument specifically designed for such use.
(3) The blasting cable or detonator circuitry shall not come in contact with energized electric equipment, including cables.
(b) Before loading boreholes with explosives, each borehole shall be cleared and its depth and direction determined.
(c) No borehole drilled beyond the depth of cut coal shall be loaded with explosives unless that portion of the borehole deeper than the cut is tamped with noncombustible material.
(d) When two working faces are approaching each other, cutting, drilling and blasting shall be done at only one working face at a time if the two faces are within 25 feet of each other.
§ 75.1317 - Primer cartridges.
(a) Primer cartridges shall be primed and loaded only by a qualified person or a person working in the presence of and under the direction of a qualified person.
(b) Primer cartridges shall not be primed until immediately before loading boreholes.
(c) Only a nonsparking punch shall be used when priming explosive cartridges.
(d) Detonators shall be completely within and parallel to the length of the cartridge and shall be secured by half-hitching the leg wires around the cartridge or secured by an equally effective method.
§ 75.1318 - Loading boreholes.
(a) Explosives shall be loaded by a qualified person or a person working in the presence of and under the direction of a qualified person.
(b) When boreholes are being loaded, no other work except that necessary to protect persons shall be done in the working place or other area where blasting is to be performed.
(c) When loading boreholes drilled at an angle of 45 degrees or greater from the horizontal in solid rock or loading long holes drilled upward in anthracite mines—
(1) The first cartridge in each borehole shall be the primer cartridge with the end of the cartridge containing the detonator facing the back of the borehole; and
(2) The explosive cartridges shall be loaded in a manner that provides contact between each cartridge in the borehole.
(d) When loading other boreholes—
(1) The primer cartridge shall be the first cartridge loaded in the borehole;
(2) The end of the cartridge in which the detonator is inserted shall face the back of the borehole; and
(3) The primer cartridge and other explosives shall be pushed to the back of the borehole in a continuous column with no cartridge being deliberately crushed or deformed.
(e) An explosive shall not be loaded into a borehole if it is damaged, deteriorated or if the cartridge is incompletely filled.
(f) Explosives of different brands, types or cartridge diameters shall not be loaded in the same borehole.
(g) Only nonconductive, nonsparking tamping poles shall be used for loading and tamping boreholes. The use of nonsparking connecting devices for extendable tamping poles is permitted.
§ 75.1319 - Weight of explosives permitted in boreholes in bituminous and lignite mines.
(a) The total weight of explosives loaded in any borehole in bituminous and lignite mines shall not exceed 3 pounds except when blasting solid rock in its natural deposit.
(b) The total weight of explosives loaded in a borehole less than 6 feet deep in bituminous and lignite mines shall be reduced by 1/2 pound for each foot of borehole less than 6 feet.
§ 75.1320 - Multiple-shot blasting.
(a) No more than 20 boreholes shall be fired in a round unless permitted in writing by the District Manager under § 75.1321.
(b) Instantaneous detonators shall not be used in the same circuit with delay detonators in any underground coal mine.
(c) In bituminous and lignite mines, only detonators with delay periods of 1,000 milliseconds or less shall be used.
(d) When blasting in anthracite mines, each borehole in a round shall be initiated in sequence from the opener hole or holes.
(e) Arrangement of detonator delay periods for bituminous and lignite mines shall be as follows:
(1) When blasting cut coal—
(i) The first shot or shots fired in a round shall be initiated in the row nearest the kerf or the row or rows nearest the shear; and
(ii) After the first shot or shots, the interval between the designated delay periods of successive shots shall be at least 50 milliseconds but not more than 100 milliseconds.
(2) When blasting coal off the solid—
(i) Each shot in the round shall be initiated in sequence from the opener hole or holes; and
(ii) After the first shot or shots, the interval between the designated delay periods of successive shots shall be at least 50 milliseconds but not more than 100 milliseconds.
§ 75.1321 - Permits for firing more than 20 boreholes and for use of nonpermissible blasting units.
(a) Applications for permits for firing more than 20 boreholes in a round and for the use of nonpermissible blasting units shall be submitted in writing to the District Manager for the district in which the mine is located and shall contain the following information:
(1) The name and address of the mine;
(2) The active workings in the mine affected by the permit and the approximate number of boreholes to be fired;
(3) The period of time during which the permit will apply;
(4) The nature of the development or construction for which they will be used, e.g., overcasts, undercasts, track grading, roof brushing or boom holes;
(5) A plan, proposed by the operator designed to protect miners in the mine from the hazards of methane and other explosive gases during each multiple shot, e.g., changes in the mine ventilation system, provisions for auxiliary ventilation and any other safeguards necessary to minimize such hazards;
(6) A statement of the specific hazards anticipated by the operator in blasting for overcasts, undercasts, track grading, brushing of roof, boom holes or other unusual blasting situations such as coalbeds of abnormal thickness; and
(7) The method to be employed to avoid the dangers anticipated during development or construction which will ensure the protection of life and the prevention of injuries to the miners exposed to such underground blasting.
(b) The District Manager may permit the firing of more than 20 boreholes of permissible explosives in a round where he has determined that it is necessary to reduce the overall hazard to which miners are exposed during underground blasting. He may also permit the use of nonpermissible blasting units if he finds that a permissible blasting unit does not have adequate blasting capacity and that the use of such permissible units will create any of the following development or construction hazards:
(1) Exposure to disturbed roof in an adjacent cavity while scaling and supporting the remaining roof prior to wiring a new series of boreholes;
(2) Exposure to underburden boreholes where prior rounds have removed the burden adjacent to a remaining borehole;
(3) Exposure to an unsupported roof while redrilling large fragmented roof rock following the loss of predrilled boreholes during earlier blasting operations; or
(4) Any other hazard created by the use of permissible blasting units during underground development or construction.
(c) Permits shall be issued on a mine-by-mine basis for periods of time to be specified by the District Manager.
(d) Permits issued under this section shall specify and include as a condition of their use, any safeguards, in addition to those proposed by the operator, which the District Manager issuing such permit has determined will be required to ensure the welfare of the miners employed in the mine at the time of the blasting permitted.
§ 75.1322 - Stemming boreholes.
(a) Only noncombustible material shall be used for stemming boreholes.
(b) Stemming materials other than water stemming bags shall be tamped to fill the entire cross sectional area of the borehole.
(c) Stemming material shall contact the explosive cartridge nearest the collar of the borehole.
(d) Each borehole 4 or more feet deep shall be stemmed for at least 24 inches.
(e) Each borehole less than 4 feet deep shall be stemmed for at least half the depth of the borehole.
(f) When blasting off the solid in bituminous and lignite mines, only pliable clay dummies shall be used for stemming.
(g) The diameter of a water stemming bag shall be within 1/4 of an inch of the diameter of the drill bit used to drill the borehole.
(h) Water stemming bags shall be constructed of tear-resistant and flame-resistant material and be capable of withstanding a 3-foot drop when filled without rupturing or developing leaks.
§ 75.1323 - Blasting circuits.
(a) Blasting circuits shall be protected from sources of stray electric current.
(b) Detonators made by different manufacturers shall not be combined in the same blasting circuit.
(c) Detonator leg wires shall be shunted until connected into the blasting circuit.
(d) Blasting cables shall be—
(1) Well insulated, copper wire of a diameter not smaller than 18-gauge; and
(2) Long enough to permit the round to be fired from a safe location that is around at least one corner from the blasting area.
(e) Blasting cables shall be shunted until immediately before firing, except when testing for circuit continuity.
(f) Wire used between the blasting cable and detonator circuitry shall—
(1) Be undamaged;
(2) Be well insulated;
(3) Have a resistance no greater than 20-gauge copper wire; and
(4) Be not more than 30 feet long.
(g) Each wire connection in a blasting circuit shall be—
(1) Properly spliced; and
(2) Separated from other connections in the circuit to prevent accidental contact and arcing.
(h) Uninsulated connections in each blasting circuit shall be kept out of water and shall not contact the coal, roof, ribs, or floor.
(i) When 20 or fewer boreholes are fired in a round, the blasting circuit shall be wired in a single series.
(j) Immediately prior to firing, all blasting circuits shall be tested for continuity and resistance using a blasting galvanometer or other instrument specifically designed for testing blasting circuits.
§ 75.1324 - Methane concentration and tests.
(a) No shot shall be fired in an area that contains 1.0 volume percent or more of methane.
(b) Immediately before shots are fired, the methane concentration in a working place or any other area where blasting is to be performed, shall be determined by a person qualified to test for methane.
§ 75.1325 - Firing procedures.
(a) Shots shall be fired by a qualified person or a person working in the presence of and under the direction of a qualified person.
(b) Only one face in a working place shall be blasted at a time, except that when blasting cut coal up to three faces may be blasted in a round if each face has a separate kerf and no more than a total of 20 shots connected in a single series are fired in the round. A permit to fire more than 20 boreholes in a round under the provisions of 30 CFR 75.1320 and 75.1321 may not be obtained for use when blasting multiple faces.
(c) Before blasting—
(1) All persons shall leave the blasting area and each immediately adjacent working place where a hazard would be created by the blast, to an area that is around at least one corner from the blasting area;
(2) The qualified person shall ascertain that all persons are a safe distance from the blasting area; and
(3) A warning shall be given and adequate time allowed for persons to respond.
(d) All shots shall be fired promptly, after all persons have been removed to a safe location.
§ 75.1326 - Examination after blasting.
(a) After blasting, the blasting area shall not be entered until it is clear of smoke and dust.
(b) Immediately after the blasting area has cleared, a qualified person or a person working in the presence of and under the direction of a qualified person, shall examine the area for misfires, methane and other hazardous conditions.
(c) If a round has partially detonated, the qualified person shall immediately leave the area and no person shall reenter the affected area for at least 5 minutes.
§ 75.1327 - Misfires.
(a) When misfires occur, only work by a qualified person to dispose of misfires and other work necessary to protect persons shall be done in the affected area.
(b) When a misfire cannot be disposed of—
(1) A qualified person shall post each accessible entrance to the area affected by the hazard of the misfire with a warning at a conspicuous location to prohibit entry; and
(2) The misfire shall be immediately reported to mine management.
§ 75.1328 - Damaged or deteriorated explosives and detonators.
(a) Damaged explosives or detonators shall be—
(1) Placed in separate containers constructed of nonconductive and nonsparking materials; and
(2) Removed from the mine or placed in a magazine and removed when the magazine is resupplied.
(b) Damaged detonators shall be shunted, if practicable, either before being removed from the mine or placed in a magazine.
(c) Deteriorated explosives and detonators shall be handled and disposed of in accordance with the instructions of the manufacturer.