Collapse to view only § 460.203 - Service hot water.
- § 460.201 - Duct system.
- § 460.202 - Thermostats and controls.
- § 460.203 - Service hot water.
- § 460.204 - Mechanical ventilation fan efficacy.
- § 460.205 - Equipment sizing.
§ 460.201 - Duct system.
Each manufactured home equipped with a duct system, which may include air handlers and filter boxes, must be sealed to limit total air leakage to less than or equal to four (4) cubic feet per minute per 100 square feet of conditioned floor area at a pressure differential of 0.1 inch w.g. (25 Pascals) across the system. Building framing cavities must not be used as ducts or plenums when directly connected to mechanical systems. The duct total air leakage requirements are adapted from section R403 of the 2021 IECC.
§ 460.202 - Thermostats and controls.
(a) At least one thermostat must be provided for each separate heating and cooling system installed by the manufacturer. The thermostat and controls requirements are adapted from section R403 of the 2021 IECC.
(b) Any programmable thermostat installed by the manufacturer that controls the heating or cooling system must—
(1) Be capable of controlling the heating and cooling system on a daily schedule to maintain different temperature set points at different times of the day and different days of the week;
(2) Include the capability to set back or temporarily operate the system to maintain zone temperatures down to 55 °F (13 °C) or up to 85 °F (29 °C); and
(3) Initially be programmed with a heating temperature set point no higher than 70 °F (21 °C) and a cooling temperature set point no lower than 78 °F (26 °C).
(c) Heat pumps with supplementary electric-resistance heat must be provided with controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
§ 460.203 - Service hot water.
(a) Service hot water systems installed by the manufacturer must be installed according to the service hot water manufacturer's installation instructions. Where service hot water systems are installed by the manufacturer, the manufacturer must ensure that any maintenance instructions received from the service hot water system manufacturer are provided with the manufactured home. The service hot water requirements are adapted from section R403 of the 2021 IECC.
(b) Any automatic and manual controls, temperature sensors, pumps associated with service hot water systems must provide access.
(c) Heated water circulation systems must—
(1) Be provided with a circulation pump;
(2) Ensure that the system return pipe is a dedicated return pipe or a cold water supply pipe;
(3) Not include any gravity or thermosyphon circulation systems;
(4) Ensure that controls for circulating heated water circulation pumps start the pump based on the identification of a demand for hot water within the occupancy; and
(5) Ensure that the controls automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water.
(d) All hot water pipes—
(1) Outside conditioned space must be insulated to a minimum R-value of R-3; and
(2) From a service hot water system to a distribution manifold must be insulated to a minimum R-value of R-3.
§ 460.204 - Mechanical ventilation fan efficacy.
(a) Whole-house mechanical ventilation system fans must meet the minimum efficacy requirements set forth in table 1 to 460.204(a), except as provided in paragraph (b) of this section. The mechanical ventilation fan efficacy requirements are adapted from section R403 of the 2021 IECC.
Table 1 to § 460.204
Fan type description | Airflow rate
minimum (cfm) | Minimum
efficacy (cfm/watt) | Heat recovery ventilator or energy recovery ventilator | Any | 1.2 | In-line supply or exhaust fans | Any | 3.8 | Other exhaust fan | <90 | 2.8 | Other exhaust fan | ≥90 | 3.5 |
---|
(b) Mechanical ventilation fans that are integral to heating, ventilating, and air conditioning equipment, including furnace fans as defined in § 430.2 of this subchapter, are not subject to the efficiency requirements in paragraph (a) of this section.
§ 460.205 - Equipment sizing.
Sizing of heating and cooling equipment installed by the manufacturer must be determined in accordance with ACCA Manual S (incorporated by reference; see § 460.3) based on building loads calculated in accordance with ACCA Manual J (incorporated by reference; see § 460.3). The equipment sizing criteria are adapted from section R403 of the 2021 IECC.