Collapse to view only § 435.200 - Scope 1 Fossil fuel-generated energy consumption requirement.
- § 435.200 - Scope 1 Fossil fuel-generated energy consumption requirement.
- § 435.201 - Scope 1 Fossil fuel-generated energy consumption determination.
- § 435.202 - Petition for downward adjustment.
- APPENDIX Appendix A - Appendix A to Subpart B of Part 435 Maximum Allowable Fossil Fuel Generated Energy Consumption
§ 435.200 - Scope 1 Fossil fuel-generated energy consumption requirement.
(a) New EISA-Subject buildings. (1) New Federal buildings that are low-rise residential buildings, for which design for construction began on or after May 1, 2025, must be designed to meet the requirements of paragraph (c) of this section if:
(i) For all leased buildings, the construction cost of the new building exceeds GSA's Annual Prospectus Thresholds that are found at www.gsa.gov/real-estate/design-construction/gsa-annual-prospectus-thresholds.
(ii) For all Federally owned non-public buildings, the cost of the building is at least $2,500,000 (in 2007 dollars, adjusted for inflation). For the purposes of calculating this threshold, agencies must set the Bureau of Labor and Statistics CPI Inflation calculator to $2,500,000 in October of 2006 (to represent the value of the original cost threshold) and then set for October of the FY during which the design for construction of the project began or is set to begin.
(b) Major renovations of EISA-Subject buildings. (1) Major renovations to Federal buildings that are low-rise residential buildings, for which design for construction began on or after May 1, 2025, must be designed to meet the requirements of paragraph (c) of this section if the cost of the major renovation is at least $2,500,000 (in 2007 dollars, adjusted for inflation). For the purposes of calculating this threshold, projects should set the Bureau of Labor and Statistics CPI Inflation calculator to $2,500,000 in October of 2006 (to represent the value of the original cost threshold) and then set for October of the FY during which the design for construction of the project began or is set to begin.
(2) This subpart applies only to the portions of the proposed building or proposed building systems that are being renovated and to the extent that the scope of the renovation permits compliance with the applicable requirements in this subpart. Unaltered portions of the proposed building or proposed building systems are not required to comply with this subpart.
(3) For leased buildings, this subpart applies to major renovations only if the proposed building was originally built for the use of any Federal agency, including for the purpose of being leased by a Federal agency.
(c) Federal buildings that are of the type included in Appendix A of this subpart—(1) New Construction and Major Renovations of all Scope 1 Fossil Fuel-Using Systems in an EISA-Subject Building.
(i) Design for construction began during FY 2024 through FY 2029. For new construction or major renovations of all fossil fuel-using systems in an EISA-subject building, for which design for construction or renovation, as applicable, began during FY 2024 through 2029, the Scope 1 fossil fuel-generated energy consumption of the proposed building, based on the building design and calculated according to § 435.201(a), must not exceed the value identified in Tables A-1a to A-2a (if targets based on Scope 1 emissions are used) or Tables A-1b to A-2b (if targets based on kBtu of fossil fuel usage are used) of Appendix A of this subpart for the associated building type, climate zone, and fiscal year in which design for construction began.
(A) Federal agencies may apply a shift adjustment multiplier to the values in Tables A-1a to A-2a or Tables A-1b to A-2b based on the following baseline hours of operation assumed in Tables A-1a to A-2a or Tables A-1b to A-2b.
(B) To calculate the shift adjustment multiplier, agencies shall estimate the number of shifts for their new building and multiply by the appropriate factor shown below in Table 1 for their building type. The Scope 1 fossil fuel-generated energy consumption target for the building would be the value in either Tables A-1a to A-2a or Tables A-1b to A-2b multiplied by the multiplier calculated in the previous sentence.
Table 1—Shift Adjustment Multiplier by Hours of Operation and Building Type
Building activity/type | Weekly hours of operation | 50 or less | 51 to 167 | 168 | Admin/professional office | 1 | 1 | 1.4 | Bank/other financial | 1 | 1 | 1.4 | Government office | 1 | 1 | 1.4 | Medical office(non-diagnostic) | 1 | 1 | 1.4 | Mixed-use office | 1 | 1 | 1.4 | Other office | 1 | 1 | 1.4 | Laboratory | 1 | 1 | 1.4 | Distribution/shipping center | 0.7 | 1.4 | 2.1 | Nonrefrigerated warehouse | 0.7 | 1.4 | 2.1 | Convenience store | 1 | 1 | 1.4 | Convenience store with gas | 1 | 1 | 1.4 | Grocery store/food market | 1 | 1 | 1.4 | Other food sales | 1 | 1 | 1.4 | Fire station/police station | 0.8 | 0.8 | 1.1 | Other public order and safety | 0.8 | 0.8 | 1.1 | Medical office (diagnostic) | 1 | 1 | 1.5 | Clinic/other outpatient health | 1 | 1 | 1.5 | Refrigerated warehouse | 1 | 1 | 1 | Religious worship | 0.9 | 1.7 | 1.7 | Entertainment/culture | 0.8 | 1.5 | 1.5 | Library | 0.8 | 1.5 | 1.5 | Recreation | 0.8 | 1.5 | 1.5 | Social/meeting | 0.8 | 1.5 | 1.5 | Other public assembly | 0.8 | 1.5 | 1.5 | College/university | 0.8 | 1.3 | 1.3 | Elementary/middle school | 0.8 | 1.3 | 1.3 | High school | 0.8 | 1.3 | 1.3 | Preschool/daycare | 0.8 | 1.3 | 1.3 | Other classroom education | 0.8 | 1.3 | 1.3 | Fast food | 0.4 | 1.1 | 2.1 | Restaurant/cafeteria | 0.4 | 1.1 | 2.1 | Other food service | 0.4 | 1.1 | 2.1 | Hospital/inpatient health | 1 | 1 | 1 | Nursing home/assisted living | 1 | 1 | 1 | Dormitory/fraternity/sorority | 1 | 1 | 1 | Hotel | 1 | 1 | 1 | Motel or inn | 1 | 1 | 1 | Other lodging | 1 | 1 | 1 | Vehicle dealership/showroom | 0.8 | 1.2 | 1.8 | Retail store | 0.8 | 1.2 | 1.8 | Other retail | 0.8 | 1.2 | 1.8 | Post office/postal center | 0.7 | 1.5 | 1.5 | Repair shop | 0.7 | 1.5 | 1.5 | Vehicle service/repair shop | 0.7 | 1.5 | 1.5 | Vehicle storage/maintenance | 0.7 | 1.5 | 1.5 | Other service | 0.7 | 1.5 | 1.5 | Strip shopping mall | 1 | 1 | 1 | Enclosed mall | 1 | 1 | 1 | Bar/Pub/Lounge | 1 | 1 | 1.4 | Courthouse/Probation Office | 1 | 1 | 1.4 |
---|
(ii) Design for construction began during or after FY 2030. For new construction and major renovations of all Scope 1 fossil fuel-using systems in an EISA-subject building, the Scope 1 fossil fuel-generated energy consumption of the proposed building, based on building design and calculated according to § 435.201(a), must be zero.
(2) Major Renovations of a Scope 1 Fossil Fuel-Using Building System or Component within an EISA-Subject Building shall follow the renovation requirements in section 4.2.1.3 of the applicable building baseline energy efficiency standards listed in § 435.4 substituting the term “design for construction” with “design for renovation” for the relevant date, and shall replace all equipment that is included in the renovation with all electric or non-fossil fuel-using ENERGY STAR or FEMP designated products as defined in § 436.42. For component level renovations, Agencies shall replace all equipment that is part of the renovation with all electric or non-fossil fuel-using ENERGY STAR or FEMP designated products as defined in § 436.42.
(d) EISA-Subject buildings that are of the type not included in Appendix A of this subpart—(1) Process load buildings. For building types that are not included in any of the building types listed in Tables A-1a to A-2a or A-1b to A-2b of appendix A of this subpart, or for building types in these tables that contain significant process loads, Federal agencies must select the applicable building type, climate zone, and fiscal year in which design for construction began from Tables A-1a to A-2a or A-1b to A-2b of appendix A of this subpart that most closely corresponds to the proposed building without the process load. The estimated Scope 1 fossil fuel-generated energy consumption of the process load must be added to the maximum allowable Scope 1 fossil fuel-generated energy consumption of the applicable building type for the appropriate fiscal year and climate zone to calculate the maximum allowable Scope 1 fossil fuel-generated energy consumption for the building. The same estimated Scope 1 fossil fuel-generated energy consumption of the process load that is added to the maximum allowable Scope 1 fossil fuel-generated energy consumption of the applicable building must also be used in determining the Scope 1 fossil fuel-generated energy consumption of the proposed building.
(2) Mixed-use buildings. For buildings that combine two or more building types with process loads or, alternatively, that combine one or more building types with process loads with one or more building types in Tables A-1a toA-2a or A-1b to A-2b of appendix A of this subpart, the maximum allowable Scope 1 fossil fuel-generated energy consumption of the proposed building is equal to the averaged process load building values determined under paragraph (d)(1) of this section and the applicable building type values in Tables A-1a toA-2a or A-1b to A-2b of appendix A of this subpart, weighted by floor area. Equation 1 shall be used for mixed use buildings.
Equation 1: Scope 1 Fossil fuel generated energy consumption for a mixed-use building = the sum across all building uses of (the fraction of total floor building floor area for building use i times the allowable fossil fuel-generated energy consumption for building use i)Equation 1 may be rewritten as:
§ 435.201 - Scope 1 Fossil fuel-generated energy consumption determination.
(a) The Scope 1 fossil fuel-generated energy consumption of a proposed design is calculated as follows:
Equation: Scope 1 Fossil Fuel-Generated Energy Consumption = Direct Fossil Fuel Consumption of Proposed Building/Floor Area Where: Direct Scope 1 Fossil Fuel-Generated Energy Consumption of Proposed Building equals the total site Scope 1 fossil fuel-generated energy consumption of the proposed building calculated in accordance with the method required in § 435.5(d), and measured in thousands of British thermal units per year (kBtu/yr), except that this term does not include fossil fuel consumption for emergency electricity generation. Agencies must include all on-site fossil fuel use or Scope 1 emissions associated with non-emergency generation from backup generators (such as those for peak shaving or peak shifting). Any energy generation or Scope 1 emissions associated with biomass fuels are excluded. Any emissions associated with natural gas for alternatively fueled vehicles (“AFVs”) (or any other alternative fuel defined at 42 U.S.C. 13211 that is provided at a Federal building) is excluded. For buildings with manufacturing or industrial process loads, such process loads shall be accounted for in the analysis for the building's fossil fuel consumption and GHG emissions, but the process loads are not subject to the phase down targets. Floor Area is the floor area of the structure that is enclosed by exterior walls, including finished or unfinished basements, finished or heated space in attics, and garages if they have an uninsulated wall in common with the house. Not included are crawl spaces, and sheds and other buildings that are not attached to the house.§ 435.202 - Petition for downward adjustment.
(a) New Federal buildings major renovations of all Scope 1 fossil fuel-using systems, and major renovations of a Scope 1 fossil fuel-using building system or component in an EISA-subject building. (1) Upon petition by a Federal agency, the Director of FEMP may adjust the applicable maximum allowable Scope 1 fossil fuel energy consumption standard with respect to a specific building, upon written certification from the head of the agency designing the building, that the requested adjustment is the largest feasible reduction in Scope 1 fossil fuel energy consumption that can practicably be achieved in light of the specified functional needs for that building, as demonstrated by:
(i) A statement from the Head of the Agency or their designee requesting the petition for downward adjustment for the building or renovation, that the building or renovation reduces consumption of Scope 1 fossil fuel energy consumption in accordance with the applicable energy performance standard to the maximum extent practicable and that each fossil fuel using product included in the proposed building that is of a product category covered by the ENERGY STAR program or FEMP for designated products is an ENERGY STAR product or a product meeting the FEMP designation criteria, as applicable;
(ii) A description of the systems, technologies, and practices that were evaluated and unable to meet the required fossil fuel reduction including a justification of why achieving the Scope 1 fossil fuel-based energy consumption targets would be technically impracticable; and
(iii) Any other information the agency determines would help explain its request.
(2) The head of the agency designing the building, or their designee, must also include the following information in the petition:
(i) A general description of the building or major renovation, including but not limited to location, use type, floor area, stories, expected number of occupants and occupant schedule, project type, project cost, and functional needs, mission critical activity, research, and national security operations as applicable;
(ii) The maximum allowable Scope 1 fossil fuel energy consumption for the building from paragraphs (c) or (d) of this section;
(iii) The estimated Scope 1 fossil fuel energy consumption of the proposed building; and
(iv) A description of the proposed building's energy-related features, such as:
(A) HVAC system or component type and configuration;
(B) HVAC equipment sizes and efficiencies;
(C) Ventilation systems or components (including outdoor air volume, controls technique, heat recovery systems, and economizers, if applicable);
(D) Service water heating system or component configuration and equipment (including solar hot water, wastewater heat recovery, and controls for circulating hot water systems, if applicable);
(E) Estimated industrial process loads; and
(F) Any other on-site fossil fuel using equipment.
(3) (i) Agencies may file one petition for a project with multiple buildings if the buildings are
(A) Of the same building, building system, or component type and of similar size and location;
(B) Are being designed and constructed to the same set of targets for fossil fuel-generated energy consumption reduction; and
(C) Would require similar measures to reduce fossil fuel-generated energy consumption and similar adjustment to the numeric reduction requirement.
(ii) The bundled petition must include the information in section (a) that pertains to all buildings, building systems or components included in the petition and an additional description of the differences between each of the buildings, building systems or components. The agency is only required to show work for adjustment once.
(4) Petitions for downward adjustment should be submitted to [email protected], or to:
U.S. Department of Energy, FEMP, Director, Clean Energy Reduction Petitions, EE-5F, 1000 Independence Ave. SW, Washington, DC 20585-0121.
(5) The Director will make a best effort to notify the requesting agency in writing whether the petition for downward adjustment to the numeric reduction requirement is approved or rejected, in 30 calendar days of submittal of a complete petition. If the Director rejects the petition or establishes a value other than that presented in the petition, the Director will forward the reasons for rejection to the petitioning agency.
(b) Exclusions. The General Services Administration (GSA) may not submit petitions under paragraphs (a) of this section. Agencies that are tenants of GSA buildings for which the agency, not GSA, has significant design control may submit petitions in accordance with this section.
Appendix A - Appendix A to Subpart B of Part 435 Maximum Allowable Fossil Fuel Generated Energy Consumption
(a) For purposes of the tables in this appendix, the climate zones are listed in the performance standards required by § 435.4(a)(4)(i).
(b) For purpose of appendix A, the following definitions apply:
(1) Mobile Home means a dwelling unit built to the Federal Manufactured Home Construction and Safety Standards in 24 CFR part 3280, that is built on a permanent chassis and moved to a site. It may be placed on a permanent or temporary foundation and may contain one or more rooms.
(2) Multi-Family in 2-4 Unit Buildings means a category of structures that is divided into living quarters for two, three, or four families or households in which one household lives above or beside another. This category also includes houses originally intended for occupancy by one family (or for some other use) that have since been converted to separate dwellings for two to four families.
(3) Multi-Family in 5 or More Unit Buildings means a category of structures that contain living quarters for five or more households or families and in which one household lives above or beside another.
(4) Single-Family Attached means a building with two or more connected dwelling units, generally with a shared wall, each providing living space for one household or family. Attached houses are considered single-family houses as long as they are not divided into more than one dwelling unit and they have independent outside entrances. A single-family house is contained within walls extending from the basement (or the ground floor, if there is no basement) to the roof. Townhouses, row houses, and duplexes are considered single-family attached dwelling units, as long as there is no dwelling unit above or below another.
(5) Single-Family Detached means a separate, unconnected dwelling unit, not sharing a wall with any other building or dwelling unit, which provides living space for one household or family. A single-family house is contained within walls extending from the basement (or the ground floor, if there is no basement) to the roof. This includes modular homes but does not include mobile homes.